Topics: ASHRAE/CMR
1: Where are the three places that the discharge from an ammonia relief valve be piped?
- atmosphere, tank containing water, where the A.H.J. indicates
- underground, into drain, into mechanical room
- to chemical neutralizing tank only
- none of the above
2: A hotel is considered a _______ occupancy.
- commercial
- institutional
- residential
- mercantile
3: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- commercial occupancy
- public assembly occupancy
- institutional occupancy
- mixed occupancy
4: Liquid level gauges must be provided with what?
- A low level mark
- A relief valve
- Automatic shut-offs
- A red line
5: What is R-611’s ASHRAE Safety Code?
- B2
- B3
- C3
- A2
6: Pressure vessels having an inside diameter of 6” or less shall be protected by
- a pressure relief device
- Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
- a fusible plug
- either a fusible plug or a pressure relief device
7: What does “ultimate strength” mean?
- Design strength of the vessel or piping in a refrigeration system
- Stress at which rupture will occur
- Highest or design pressure allowed inside a machinery room
- None of the above
8: Dual-pressure relief devices should be installed on
- vessels of 10 cubic feet or less
- vessels of 3 cubic feet or less
- vessels of 3 cubic feet or more
- vessels of 10 cubic feet or more
9: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- quarterly
- annually
- bi-annually
- regularly
10: Who authorizes the form of certificate of completion of refrigeration systems that should be used?
- Supervisor or project manager in charge of the installation
- Fire Marshal
- Massachusetts Board of Boiler Rules
- Owner
11: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
12: Where a refrigeration or air conditioning system is installed,
- it shall not be operated below prescribed pressuers
- the form or certificate shall be authorized by the Department of Public Safety
- The company who installed the system must notify the fire department in the jurisdiction where installed
- A field inspection shall be made before it is put into service
13: What is R-22?
- HFC
- Chlorofluoromethane
- CCFCM
- Chlorodifluoromethane
14: A relief valve discharge capacity is rated in
- temperature minus pounds of air per second divided by release rate squared
- PSIG
- Pounds of air per minute.
- PSIA
15: Stop valves shall not be permitted between the system and the
- relief valve
- condenser
- service valve
- bleed valve
16: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.
- 90
- 100
- 80
- 110
17: Single compound Refrigerants are classified by what two criteria?
- Weight and color
- Temperature range and hazardousness
- Flammability and toxicity
- Flammability and temperature range
18: Ammonia can come in contact with _______ ?
- Brass
- Copper tubing
- Aluminum
- Copper
19: Name an HCFC refrigerant(s):
- R-22
- R-123
- R-11
- both a & b
20: Liquid level gauge glasses shall have automatic closing shut off valves, except Bull's eye or reflex type.
- True
- False
21: What is the definition of exit?
- Anywhere where a stairwell leads to outdoors
- The separated fire-resistant portion of a means of egress providing a protected travel path between the exit access and the exit discharge
- Any doorway or pathway unobstructed for access to anywhere considered safe
- Both a & b
22: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
23: High pressure controls should be set no higher than
- 90% of set point
- 80% of set point
- 25% of set point
- 10% of set point
24: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
25: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above