Massachusetts Refrigeration Tech/Contractors practice quiz
ASHRAE/CMR code Prep Quiz
Topics: ASHRAE/CMR
1: B3 refrigerants are considered
non-toxic but non-flammable
non-toxic but flammable
toxic but non-flammable
toxic and highly flammable
2: The Department that certifies the transportation of refrigerant is the
EPO
DOT
EPA
RSES
3: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
compressor
outside the machinery room
boiler
evaporator
4: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants
higher
there is no Group B1 refrigerants
lower
the same
5: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
shall have a pressure limiting device installed on the high side of the system
does not require a pressure-limiting device
shall be inspected by the Boiler of Inspectors bi-annually
shall have a pressure limiting device and a pressure relief valve installed
6: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.
50
15
75
55
7: What do you need to do when you install a new system?
Have it inspected
Document the superheat and subcooling reading
Add refrigerant
Insulate the suction line before you take a superheat reading
8: When a pressure gauge is permanently installed on a system, it must be ___ times the design pressure of the system.
1.2
1
2.2
1.5
9: R-22 falls under which safety classification?
A-1
A-2
B-2
B-1
10: Which refrigerant was still able to be vented to the atmosphere after July 1, 1992?
R-12
R-113
R-22
R-11
11: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
Flush with R-11
Flush with RX-11
Flush with ammonia
Flush with R-718
12: How many flammability classifications are refrigerants in?
5
2
7
3
13: A pressure relief should be located at least _______ from windows and doors.
15'
20'
30'
25'
14: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.
50
75
20
15
15: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a
mercantile occupancy
commercial occupancy
business occupancy
public assembly occupancy.
16: Pressure vessels of 10 cubic feet or more gross volume shall use
at least one rupture member
a dual pressure-relief valve if charging into the atmosphere
at least three means of discharge and/or rupture discs
both a and b are correct
17: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
annually
quarterly
regularly
bi-annually
18: What happens after your initial inspection of a pressure vessel?
There is a temporary shut-down until a final inspection can be performed.
Notify the AHJ to let them know that the system been inspected
Notify the Fire Marshal that the system has been inspected and approved
Inspector leaves a metal tag with a certification listed on it
19: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within
2 months
1 week
14 days
30 days
20: What is a Category "M" fluid?
A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
Any fluid that exceeds 150 psig and has design temperatures over 366F
A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
A typical refrigerant used on newer air conditioning and heat pump systems
21: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
Place sign, check for leaks, and insulate suction line
Make sure its compatible, notify owner, and notify AHJ.
you can never change refrigerants
Nothing must be done
22: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
10
18
15
24
23: What is R-22?
HFC
Chlorodifluoromethane
CCFCM
Chlorofluoromethane
24: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
100
350
550
50
25: Doors communicating with outside from a mechanical room must be?