Topics: ASHRAE/CMR
1: R-123 belongs to Group
- B-2
- B-1
- A-3
- B-3
2: Where are the three places that the discharge from an ammonia relief valve be piped?
- atmosphere, tank containing water, where the A.H.J. indicates
- underground, into drain, into mechanical room
- to chemical neutralizing tank only
- none of the above
3: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- phosgene gas sening
- CO Sensing
- A group sensing
- refrigerant sensing
4: The certificate of inspection
- shall be posted on the compressor shell or electrical panel at the unit
- shall be authorized by a notarized insurance company
- shall be posted and protected from dirt, water, and other elements
- shall be $20 and an additional fee of $1 for each tone above 20 tons
5: All electrical work done on refrigeration systems must comply with
- OSHA
- Department of Energy
- ASHREA-15 Section 9.2.1
- NEC and Massachusetts Modifications
6: When a receiver is greater than 3 cubic feet but less than 10 cubic feed, what is the minimum relief device required?
- fusible plug
- relief valve
- rupture disc
- all of the above
7: A High-Probability System
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
- is such that a leak of refrigerant from a failed connection will enter the occupied space
8: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.
- 100
- 80
- 110
- 90
9: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within
- 14 days
- 2 months
- 30 days
- 1 week
10: Setting a pressure relief device shall not exceed ___ of the design pressure
- 90%
- 100%
- 80%
- 75%
11: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
- evaporator
- compressor
- boiler
- outside the machinery room
12: What do you need to do when you install a new system?
- Document the superheat and subcooling reading
- Add refrigerant
- Insulate the suction line before you take a superheat reading
- Have it inspected
13: Liquid level gauges shall have _____________ with one exception being that of the liquid level gauge bull’s eye type.
- color-coded glass to determine type of refrigerant
- moisture indicators
- automatic closing shut-off valves
- All of the above
14: The gauge thickness required on a CO2 tank construction is
- 5/16"
- 1/8"
- 1/16"
- 3/32"
15: Who approves containers for refrigerants?
- D.O.D
- D.O.T
- D.O.E
- E.P.A
16: Pressure vessels with an internal volume of 3 cubic feet or more
- shall use fusible plugs
- do not need pressure relief protection
- shall use pressure relief devices
- shall use pressure relief devices or fusible plugs
17: R-410A is classified as a ____ refrigerant on the safety matrix.
- B-2
- A-1
- B-1
- A-2
18: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
- 18
- 10
- 15
- 24
19: What must be done if refrigeration lines pass through a concrete floor?
- leak checked
- moisture barrier
- installed through a pipe casing
- insulated
20: Evaporators within 18" of a heating coil must be equipped with a
- pressure relief device
- zone valve
- low limit control
- high limit control
21: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
22: What refrigerant doesn't have to be classifted?
- R-717
- R-718
- R-134a
- R-711
23: Name three things that must be done when changing refrigeration lubricant?
- Make sure it's compatible, notify owner, notify AHJ
- You can't change lubricants.
- Nothing must be done
- Place sign, check for leaks, insulate
24: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 55 lbs
- 500 lbs
- 330 lbs
- 660 lbs
25: An example of direct system is
- rooftop unit
- chiller
- absorber
- none of the above