Topics: ASHRAE/CMR
1: Which refrigerant replaced R-12?
- R-407A
- R-410A
- R-22
- R-134A
2: Pipe identification labels are required when the system contains more than
- 120 lbs
- 110 lbs
- 55 lbs
- 65 lbs
3: Low temperature systems should have what?
- High pour point
- Low pour point
- High viscosity
- None of the above
4: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- nothing must be done
- place sign, check for leaks, insulate
- you can't change refrigerants
- make sure it's compatible, notify owner, notify A.H.J
5: Pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 33
- 22
- 18
- 50
6: Evaporators within 18" of a heating coil must be equipped with a
- high limit control
- zone valve
- low limit control
- pressure relief device
7: How are refrigerant blends classified?
- Based on the oil used
- Based on best case Fractionation
- Blends don't have to be classified
- Based on worst case fractionation
8: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 100
- 100,000
- 1,000
- 10,000
9: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 22
- 66
- 50
- 25
10: R-717 is
- trichloromethane
- water
- carbon dioxide
- ammonia
11: Name a CFC refrigerant(s):
- R-11
- R-12
- R-123
- both a & b
12: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.
- 50
- 55
- 75
- 15
13: What type of material can't be used on the outlet of a relief valve?
- Stainless steel
- Magnesium alloy
- PVC
- Copper
14: What type of refrigerants are NOT flammable?
- CHC
- HFC
- HCFC
- All of the above
15: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
16: When testing systems using non-positive displacement compressors, the entire system shall be considered for test purposes as the low side.
- True
- False
17: How far from the ground does a relief valve need to be?
- At least 15' above grade
- At least 20' above grade
- At least 25' above grade
- Not more than 3' above grade
18: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of
- the high side
- the aggregate of the high side and low side
- 2.5 times the design pressure
- the low side
19: How much refrigerant can be stored in a mechanical room outside of the system?
- 150
- 200
- 330
- 100
20: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants
- lower
- there is no Group B1 refrigerants
- the same
- higher
21: Institutional occupancy is
- a premise or that portion of a premise where large numbers of people congregate and from which occupants cannot quickly vacate the space.
- a premise or that portion of a premise from which, because they are disabled, debilitated, or confined, occupants cannot readily leave without the assistance of others.
- a premise or that portion of a premise where people transact business, receive personal service, or purchase food and other goods.
- None of the above
22: What is the refrigerant chlorodifluoromethane?
- R-12
- R-123
- R-134a
- R-22
23: Each machinery room shall contain
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- high and low pressure controls
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
24: Pressure relief valves shall be marked with the data from
- Section XIII Division of the ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section I Division VIII of ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
25: What would be the classification of a prison?
- Institutional
- Place of assembly
- Industrial
- Large mercantile