Topics: ASHRAE/CMR
1: Each machinery room shall contain
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- high and low pressure controls
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
2: Pressure relief devices are marked with a ____________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- UM or UL
- UV or UR
- UL and UM
- UL and UR
3: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants
- higher
- there is no Group B1 refrigerants
- lower
- the same
4: Evaporators within 18" of a heating coil must be equipped with a
- low limit control
- pressure relief device
- high limit control
- zone valve
5: What refrigerant doesn't have to be classified?
- R-717
- R-422A
- R-134A
- R-718
6: Joints in refrigeration piping must be _____ before being covered?
- Pressurized
- Inspected
- Leak tested
- Insulated
7: Ammonia (NH3) is a group III refrigerant
- True
- False
8: A Low-Probability System
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is a system highly likely to leak form a failed connection or component of such system
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is such that a leak of refrigerant from a failed connection can not enter the occupied space
9: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- refrigerant sensing
- CO Sensing
- phosgene gas sening
- A group sensing
10: A High-Probability System
- is a system highly likely to leak form a failed connection or component of such system
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
11: The Department that certifies the transportation of refrigerant is the
- RSES
- EPO
- DOT
- EPA
12: When should a relief valve start to function?
- 10 psi before it's set pressure
- Before the purge station discharges
- Two times it's working pressure
- At it's set pressure
13: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
14: Name three things that must be done when changing refrigeration lubricant?
- You can't change lubricants.
- Make sure it's compatible, notify owner, notify AHJ
- Nothing must be done
- Place sign, check for leaks, insulate
15: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
16: R-11 belongs to Group
- B-3
- A-1
- B-1
- A-2
17: A class A3 refrigerant is considered
- non-toxic and non-flammable
- non-toxic but highly flammable
- toxic and non-flammable
- toxic and somewhat flammable
18: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
19: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
20: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
21: What must be done to refrigerant pipes before being buried?
- Coated
- Encased
- Leaked checked
- Certified
22: What section governs pressure vessels?
- Section ASHREA 34
- Section 8 ASHREA 15 ASME unfired
- Section 1 ASHREA 15 ASME fired
- OSHA
23: All electrical work done on refrigeration systems must comply with
- OSHA
- Department of Energy
- NEC and Massachusetts Modifications
- ASHREA-15 Section 9.2.1
24: R-22 is classified as a ____ refrigerant on the safety matrix.
- A-2
- A-1
- B-2
- B-1
25: Class 3 refrigerants are
- highly flammable
- toxic
- non-flammable
- non-toxic