ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: How many different groups of refrigerants are there?

  • 3
  • 15
  • 7
  • 11

2: The ____ design is the maximum pressure for which a specific part of a refrigeration system is designed.

  • low pressure
  • high pressure
  • critical pressure
  • design pressure

3: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested

  • quarterly
  • annually
  • bi-annually
  • regularly

4: What must be done to refrigerant pipes before being buried ?(8.10.4)

  • Certified
  • Insulated and installed in a pipe duct (Encased)
  • Leak checked
  • Classifed

5: System design pressures must take into consideration, not only, pressures found during normal operation but also what?

  • When it's cold out
  • When there is a malfunction on the high side
  • When its warm out
  • All of the above

6: High pressure controls should be set no higher than

  • 90% of set point
  • 80% of set point
  • 25% of set point
  • 10% of set point

7: Pressure vessels shall be provided with ___________in accordance with Section VIII of the ASME Boiler & Pressure Vessel Code

  • over pressure protection
  • Pressure vessels need no type of protection as long as it is hydrostatically tested every three months
  • over pressure protection and a rupture disc
  • over pressure protection as well as a temperature protection device

8: A class A3 refrigerant is considered

  • non-toxic and non-flammable
  • toxic and non-flammable
  • non-toxic but highly flammable
  • toxic and somewhat flammable

9: When is the only time you can leave a service container attached to a system?

  • Leaking system
  • Recovery
  • Charging
  • Both b and c

10: How much clearance do you need around the perimeter of electrical panels?

  • 18"
  • 24"
  • 12"
  • 36"

11: Who approves containers for refrigerants?

  • D.O.E
  • E.P.A
  • D.O.T
  • D.O.D

12: What was the main reason for enacting the no venting rule of July 1, 1992?

  • Ozone depletion
  • Green house effect
  • Global warming potential
  • All of the above

13: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed

  • 330 lbs
  • 500 lbs
  • 660 lbs
  • 55 lbs

14: How many refrigerant classifications are there for toxicity?

  • 3
  • 5
  • 1
  • 2

15: What refrigerant has zero ozone depletion

  • HFC
  • CFC
  • HCFC
  • None of the above

16: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a

  • business occupancy
  • public assembly occupancy.
  • commercial occupancy
  • mercantile occupancy

17: What is the intention of the word “should” as used in the code?

  • A mandatory requirement
  • A recommendation or advisory guideline
  • A technician’s choice of how it should be done
  • None of the Above

18: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8

  • the liquid side of the system
  • the vapor side of the system
  • high side of the system
  • low side of the system

19: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.

  • lower
  • the same
  • there is no Group B1 refrigerants
  • higher

20: When releasing a hydrogenated hydrocarbon refrigerant to the atmosphere, ample ventilation must be provided and

  • gas masks must be worn
  • explosion precautions must be taken
  • the owner shall be informed
  • no flames shall be permitted

21: Which of the following is an inorganic refrigerant?

  • R-22
  • Ammonia
  • Chlorofluorocarbons
  • All of the above

22: What type of material can't be used on the outlet of a relief valve?

  • Copper
  • Stainless steel
  • PVC
  • Magnesium alloy

23: What is an egress?

  • A valve put on the low side of the system to prevent frosting
  • An entrance or exit
  • A code violation
  • An escape route

24: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?

  • 1,000
  • 10,000
  • 100
  • 100,000

25: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?

  • When there is a space 6' or more above it
  • When it's used as part of a supply or return air system
  • When its white
  • When there are sprinklers above