ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: Refrigeration piping before being buried shall be

  • leak tested
  • encased in pipe duct
  • pressure tested
  • All of the above

2: When is the only time you can leave a service container attached to a system?

  • Leaking system
  • Recovery
  • Charging
  • Both b and c

3: What is an egress?

  • A valve put on the low side of the system to prevent frosting
  • An entrance or exit
  • An escape route
  • A code violation

4: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the

  • breaker panel in
  • load-side of the contactor in
  • 24 volt secondary side of the Class 2 transformer to the thermostat
  • first disconnect in

5: How many refrigerant classifications are there for toxicity?

  • 5
  • 3
  • 1
  • 2

6: Class 3 refrigerants are

  • highly flammable
  • toxic
  • non-flammable
  • non-toxic

7: When a refrigeration or air conditioning system is installed

  • it shall be approved by the owner for proper operation.
  • it shall not be operated below prescribed pressures
  • a field inspection shall be made before it is put into service
  • the form of certificate shall be authorized by the Department of Pubic safety

8: How many different groups of refrigerants are there?

  • 15
  • 3
  • 7
  • 11

9: Ammonia belongs to Group

  • A-1
  • B-1
  • B-2
  • A-2

10: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.

  • 80%
  • 100%
  • 90%
  • 75%

11: Fusible plugs must have what marked on them?

  • Melting temperature in F
  • Melting temperature in C
  • Opening pressure
  • All of the above

12: Joints in refrigeration piping must be _____ before being covered?

  • Pressurized
  • Inspected
  • Leak tested
  • Insulated

13: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?

  • 1,000
  • 10,000
  • 100,000
  • 100

14: R-718 is rated unlimited for refrigeration quantity contained in a system. Why?

  • R-718 is not rated unlimited because it's a dangerous refrigerant
  • Because it's a non-flammable refrigerant
  • Because it's cheap
  • Because it's water

15: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a

  • commercial occupancy
  • public assembly occupancy.
  • mercantile occupancy
  • business occupancy

16: High pressure controls should be set no higher than

  • 80% of set point
  • 25% of set point
  • 90% of set point
  • 10% of set point

17: Name a CFC refrigerant(s):

  • R-11
  • R-12
  • R-123
  • both a & b

18: Most CFC's are

  • flammable
  • inert but toxic
  • toxic
  • inert

19: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of

  • the ASME Boiler and Pressure Vessel Code
  • Section 11.3.1.5 ASHRAE 15 Standard
  • the ANSI Standard 10.7.2
  • both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5

20: R-410A is classified as a ____ refrigerant on the safety matrix.

  • B-2
  • A-1
  • B-1
  • A-2

21: Pressure vessels with an internal volume of 3 cubic feet or less

  • shall use fusible plugs
  • shall use pressure relief devices or fusible plugs
  • shall use pressure relief devices
  • do not need pressure relief protection

22: When testing systems using non-positive displacement compressors, the entire system shall be considered for test purposes as the low side.

  • True
  • False

23: What refrigerant is an inorganic compound?

  • R-410A
  • R-22
  • Ammonia
  • R-132A

24: Fusible plugs shall not be used with pressure vessels of

  • 3 cubic feet or less
  • 3 cubic feet or more
  • 15 square feet or less
  • 15 cubic feet or more

25: A room having machinery but no flame producing apparatus permanently installed and operated is considered a

  • Class B machinery room
  • Class M machinery room
  • Class A machinery room
  • Class T machinery room