Topics: ASHRAE/CMR
1: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- the liquid side of the system
- high side of the system
- the vapor side of the system
2: What type of refrigerants are NOT flammable?
- CHC
- HFC
- HCFC
- All of the above
3: A plug containing an alloy that will melt at a specific temperature to relief pressure is a
- fusible plug
- relief plug
- fusion plug
- rupture plug
4: All serviceable components of a refrigeration system shall be provided with
- safe access
- manufactures instructions on start-up procedures
- name plates with markings referring to pressure and temperature in accordance with ASME Boiler and Pressure Vessel Code
- service manuals
5: What section of ASHRAE-15 governs pressure vessels?
- Section 7 ASHRAE-15 ASME VIII fired
- OSHA
- Section 9 ASHRAE-15 ASME VIII unfired
- Section 6 ASHRAE-34 ASME VIII unfired
6: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When it's used as part of a supply or return air system
- When there is a space 6' or more above it
- When its white
- When there are sprinklers above
7: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class A machinery room
- Class T machinery room
- Class M machinery room
- Class B machinery room
8: What is a Category "D" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
- Any fluid that exceeds 150 psig and has design temperature of over 366F
9: What must be done to refrigerant pipes before being buried ?(8.10.4)
- Leak checked
- Insulated and installed in a pipe duct (Encased)
- Classifed
- Certified
10: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
11: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- place sign, check for leaks, insulate
- you can't change refrigerants
- make sure it's compatible, notify owner, notify A.H.J
- nothing must be done
12: How many gallons of water per pound of ammonia do you need?
- 5
- 20
- 1
- 15
13: Name three things that must be done when changing refrigeration lubricant?
- Place sign, check for leaks, insulate
- Make sure it's compatible, notify owner, notify AHJ
- You can't change lubricants.
- Nothing must be done
14: Joints in piping for refrigeration containing parts must withstand temperatures of ___?
- 700F
- 1000F
- 600F
- 800F
15: What type of material can't be used on the outlet of a relief valve?
- PVC
- Magnesium alloy
- Stainless steel
- Copper
16: Which refrigerant(s) is an HFC?
- R-22
- R-410A
- R-502
- All of the above
17: Fusible plugs must have what marked on them?
- Melting temperature in F
- Melting temperature in C
- Opening pressure
- All of the above
18: Stop valves shall not be permitted between the system and the
- condenser
- service valve
- relief valve
- bleed valve
19: When is the only time you can leave a service container attached to a system?
- Leaking system
- Recovery
- Charging
- Both b and c
20: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.
- higher
- the same
- lower
- there is no Group B1 refrigerants
21: A relief valve shall be located at least ___ above grade.
- 15'
- 10'
- 25'
- 36'
22: Where are the three places that the discharge from an ammonia relief valve be piped?
- atmosphere, tank containing water, where the A.H.J. indicates
- underground, into drain, into mechanical room
- to chemical neutralizing tank only
- none of the above
23: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 330 lbs
- 55 lbs
- 660 lbs
- 500 lbs
24: What refrigerant doesn't have to be classified?
- R-422A
- R-718
- R-717
- R-134A
25: A class A3 refrigerant is considered
- non-toxic but highly flammable
- non-toxic and non-flammable
- toxic and somewhat flammable
- toxic and non-flammable