Topics: ASHRAE/CMR
1: Refrigerant piping crossing an open space that affords passageway in any building shall not be less than _____ feet above the floor unless piping is located against the ceiling.
- 9.00'
- 7.25'
- 7.00'
- 8'4"
2: The Department that certifies the transportation of refrigerant is the
- RSES
- DOT
- EPA
- EPO
3: What would be the classification of a church?
- Large mercantile
- Institutional
- Industrial
- Place of assembly
4: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- licensed technician
- licensed welder
- competent welder
- welder qualified
5: What happens after your initial inspection of a pressure vessel?
- Notify the Fire Marshal that the system has been inspected and approved
- There is a temporary shut-down until a final inspection can be performed.
- Inspector leaves a metal tag with a certification listed on it
- Notify the AHJ to let them know that the system been inspected
6: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
7: Halo-carbon refrigerants cannot be used with what material?
- Stainless Steel
- Magnesium alloy
- Copper
- Aluminum
8: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
9: There can be no airflow from an occupied space through a machine room unless what?
- System is high velocity
- System is ducted and sealed
- Duct is not located in the ceiling
- None of the above.
10: What must be done if refrigeration lines pass through a concrete floor?
- installed through a pipe casing
- moisture barrier
- leak checked
- insulated
11: Direct systems using Group II refrigerants
- shall not be used for air condition for human comfort
- shall be installed per instruction of the AHJ
- shall be installed in Class T machinery rooms
- shall be allowed to be used for human comfort.
12: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When it's used as part of a supply or return air system
- When its white
- When there is a space 6' or more above it
- When there are sprinklers above
13: How many refrigerant classifications are there for toxicity?
- 1
- 5
- 2
- 3
14: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.
- True
- False
15: What is the minimum size of the discharge pipe?
- Same size as the outlet of the relief valve
- One pipe size larger that the inlet of the relief valve
- Depends on size of manifold
- All of the above
16: A Low-Probability System
- is such that a leak of refrigerant from a failed connection can not enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is a system highly likely to leak form a failed connection or component of such system
- is such that any leak will cause injury or death to anyone within a 100 square foot area
17: Trichlorofluoromethane is the name of what refrigerant?
- R-502
- R-12
- R-11
- R-113
18: Refrigerant restricted in 2004 but used for transition for decades:
- R-123
- R-22
- R-134A
- R-11
19: Class T machine room
- shall have remote controls to stop the action of the refrigerant compressor
- has no flame producing apparatus permanently installed
- shall have refrigerant leak detecting systems installed inside and outside the room
- shall include closets used for setting equipment
20: Class 3 refrigerants are
- toxic
- highly flammable
- non-flammable
- non-toxic
21: The color code of a tank of ammonia is
- silver
- light green
- white
- lavender
22: Ammonia belongs to Group
- A-1
- B-2
- B-1
- A-2
23: When an inspection is needed, how often must it be done?
- every 36 months
- every 24 months
- every 18 months
- annually
24: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
- 15
- 10
- 18
- 24
25: Stop valves shall not be permitted between the system and the
- relief valve
- service valve
- bleed valve
- condenser