Topics: ASHRAE/CMR
1: Where a refrigeration or air conditioning system is installed,
- it shall not be operated below prescribed pressuers
- A field inspection shall be made before it is put into service
- the form or certificate shall be authorized by the Department of Public Safety
- The company who installed the system must notify the fire department in the jurisdiction where installed
2: What is not a requirement of a Class T machine room?
- Tight fitting doors
- Self-closing doors
- Fire hose connected to the building fire protection system.
- Automatic ventilation
3: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.
- containing R-11, R-123 & R-717 exclusively shall not be prohibited
- of Group B2 refrigerant shall be prohibited
- shall be prohibited
- shall not be prohibited
4: What does safe access mean?
- A clear unobstructed path to the equipment and controls
- Well-lit exit signs
- Locked doors
- OSHA approved
5: Pipe identification labels are required when the system contains more than
- 110 lbs
- 65 lbs
- 55 lbs
- 120 lbs
6: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.
- True
- False
7: What is a Category "D" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
8: Stop valves shall not be permitted between the system and the
- relief valve
- service valve
- condenser
- bleed valve
9: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 2.5, 2.5
- 6.6, 6.6
- 3.0, 3.5
- 2.5, 3.0
10: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class T machinery room
- Class B machinery room
- Class A machinery room
- Class M machinery room
11: An example of direct system is
- rooftop unit
- chiller
- absorber
- none of the above
12: Refrigeration piping before being buried shall be
- leak tested
- encased in pipe duct
- pressure tested
- All of the above
13: What is R-22?
- CCFCM
- Chlorofluoromethane
- HFC
- Chlorodifluoromethane
14: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
15: What is the refrigerant chlorodifluoromethane?
- R-123
- R-134a
- R-22
- R-12
16: How many refrigerant classifications are there for flammability?
- 1
- 2
- 3
- 7
17: A declaration test is needed when the system contains more than
- 55 lbs
- 65 lbs
- 120 lbs
- 110 lbs
18: Pressure vessels with an internal volume of 10 cubic feet or more
- shall use pressure relief devices
- shall use pressure relief devices or fusible plugs
- shall use rupture discs or duel pressure relief valves
- shall use fusible plugs
19: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.
- 15
- 75
- 55
- 50
20: A class A3 refrigerant is considered
- toxic and somewhat flammable
- non-toxic but highly flammable
- non-toxic and non-flammable
- toxic and non-flammable
21: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.
- 36
- 24
- 18
- 48
22: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
23: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- refrigerant sensing
- A group sensing
- phosgene gas sening
- CO Sensing
24: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of
- 2.5 times the design pressure
- the high side
- the low side
- the aggregate of the high side and low side
25: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
- 10
- 18
- 15
- 24