Topics: ASHRAE/CMR
1: The Board of Boilers adopts by reference
- MSCA Code
- Montreal Protocol Safety Code
- the 1997 ANSI/ASHRAE Safety Code
- the MACS Pressure Vessel Code of Massachusetts
2: How many gallons of water do you need per pound of ammonia?
- 1
- 10
- 100
- 50
3: Class 3 refrigerants are
- toxic
- non-flammable
- highly flammable
- non-toxic
4: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
5: Ammonia (NH3) is a group III refrigerant
- True
- False
6: How many different groups of refrigerants are there?
- 3
- 15
- 7
- 11
7: Pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 22
- 50
- 18
- 33
8: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.
- 36
- 48
- 18
- 24
9: All electrical work done on refrigeration systems must comply with
- OSHA
- ASHREA-15 Section 9.2.1
- NEC and Massachusetts Modifications
- Department of Energy
10: When air is ducted through a machine room that services occupied space, What must be done?
- Ducted and sealed
- Insulated and cross broke
- Flanged and gasketed
- Welded and seamed.
11: Who is permitted to access a refrigeration machine room?
- Any employee
- Anyone, it's a completely safe area
- Authorized persons only
- Contractors only
12: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Place sign, check for leaks, and insulate suction line
- Make sure its compatible, notify owner, and notify AHJ.
- Nothing must be done
- you can never change refrigerants
13: Evaporators within 18" of a heating coil must be equipped with a
- low limit control
- pressure relief device
- high limit control
- zone valve
14: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
15: What type of copper is not permitted on refrigeration systems?
- Type M
- Type L
- Type N
- Type K
16: When testing systems using non-positive displacement compressors, the entire system shall be considered for test purposes as the low side.
- True
- False
17: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 330
- 1,000
- 110
- 6.6
18: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the
- load-side of the contactor in
- 24 volt secondary side of the Class 2 transformer to the thermostat
- first disconnect in
- breaker panel in
19: No open flames are allowed in the machinery room unless?
- Approved by the authorized person
- Approved by the installing contractor
- Never can be allowed
- Only when combustion air is provided from outside of the machinery room
20: What is the intention of the word “shall” as used in the code?
- A mandatory requirement
- A recommendation or advisory guideline
- A technician’s choice of how it should be done
- None of the above
21: How many CFMs are required per square foot of commercial office occupied space
- .5 CFM
- 5 CFM
- 20 CFM
- 15 CFM
22: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- the liquid side of the system
- the vapor side of the system
- high side of the system
- low side of the system
23: What is the definition of exit?
- Anywhere where a stairwell leads to outdoors
- The separated fire-resistant portion of a means of egress providing a protected travel path between the exit access and the exit discharge
- Any doorway or pathway unobstructed for access to anywhere considered safe
- Both a & b
24: Pressure vessels with an internal volume of 3 cubic feet or less
- do not need pressure relief protection
- shall use pressure relief devices
- shall use fusible plugs
- shall use pressure relief devices or fusible plugs
25: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5