Topics: ASHRAE/CMR
1: Indirect systems using Group II refrigerants
- shall be used in refrigeration system less than 1,000 lbs
- shall be used in refrigeration system in excess of 1,000 lbs
- shall be used for mechanical equipment only
- shall have all refrigerant containing parts except piping, installed in a Class T machine room
2: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 55 lbs
- 660 lbs
- 500 lbs
- 330 lbs
3: The certificate of inspection
- shall be posted on the compressor shell or electrical panel at the unit
- shall be authorized by a notarized insurance company
- shall be $20 and an additional fee of $1 for each tone above 20 tons
- shall be posted and protected from dirt, water, and other elements
4: When is the only time you can leave a service container attached to a system?
- Leaking system
- Recovery
- Charging
- Both b and c
5: How many gallons of water per pound of ammonia do you need?
- 15
- 5
- 20
- 1
6: Can ammonia be used on domestic system?
- no
- yes
- no, unless there is proper ventilation system installed
- yes, for systems under 10 tons
7: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 550 lbs
- 660 lbs
- 330 lbs.
- 55 lbs
8: Class T machine room
- shall include closets used for setting equipment
- shall have refrigerant leak detecting systems installed inside and outside the room
- shall have remote controls to stop the action of the refrigerant compressor
- has no flame producing apparatus permanently installed
9: Direct systems using Group II refrigerants
- shall be installed per instruction of the AHJ
- shall be installed in Class T machinery rooms
- shall be allowed to be used for human comfort.
- shall not be used for air condition for human comfort
10: Pressure relief valves shall be marked with the data from
- Section I Division VIII of ASME Boiler & Pressure Code
- Section XIII Division of the ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
11: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class M machinery room
- Class T machinery room
- Class B machinery room
- Class A machinery room
12: Each machinery room shall contain
- high and low pressure controls
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
13: Ammonia belongs to Group
- B-2
- B-1
- A-2
- A-1
14: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
15: Where must a refrigeration contractor's license number be displayed?
- Trucks, license plates, and uniforms
- Trucks, invoices, and advertising
- Truck, office, every job, and on all equipment
- Uniforms, checks, and invoices.
16: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 1,000
- 6.6
- 110
- 330
17: What would be the classification of a church?
- Industrial
- Place of assembly
- Large mercantile
- Institutional
18: Setting a pressure relief device shall not exceed ___ of the design pressure
- 75%
- 80%
- 90%
- 100%
19: R-718 is rated unlimited for refrigeration quantity contained in a system. Why?
- Because it's cheap
- Because it's a non-flammable refrigerant
- Because it's water
- R-718 is not rated unlimited because it's a dangerous refrigerant
20: Which refrigerant was still able to be vented to the atmosphere after July 1, 1992?
- R-22
- R-12
- R-113
- R-11
21: The color code of a tank of ammonia is
- white
- light green
- silver
- lavender
22: Where a refrigeration or air conditioning system is installed,
- it shall not be operated below prescribed pressuers
- A field inspection shall be made before it is put into service
- The company who installed the system must notify the fire department in the jurisdiction where installed
- the form or certificate shall be authorized by the Department of Public Safety
23: Pressure vessel having an inside diameter exceeding 6” with an internal pressure greater than 15psig shall be marked directly on or on the nameplate the letters _______________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- “UM” and “UV”
- “UL”
- “UV”
- “U” or “UM”
24: What kind of material can't be used on the outlet of a relief valve?
- Stainless Steel
- Aluminum
- Copper
- PVC
25: What refrigerant has zero ozone depletion
- HFC
- CFC
- HCFC
- None of the above