Topics: ASHRAE/CMR
1: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
2: What type refrigerant is NOT ozone depleting?
- HFC
- CFC
- HCFC
- Halon
3: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- the return air ducted system
- Machinery rooms need not be vented
- the outdoors
- the mechanical room housing the refrigeration system
4: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 500 lbs
- 55 lbs
- 660 lbs
- 330 lbs
5: What should not (and can not) be located between a pressure imposing device and a pressure-limiting device?
- Moisture indicator
- Stop valve
- Muffler
- Foot valve
6: Which refrigerant class listed below is the most flammable?
- B2
- A3
- A2
- C3
7: A pressure relief should be located at least _______ from windows and doors.
- 20'
- 25'
- 15'
- 30'
8: What is not a requirement of a class T machine room?
- tight fitting doors
- fire hose connection to the building fire protection system
- self-closing doors
- automatic ventilation
9: When liquid receivers are used, the liquid refrigerant shall not exceed _______percent of the volume at 90F.
- 90%
- 75%
- 99%
- 80%
10: Pressure limiting devices are not required for systems containing less then ________ refrigerants.
- 13.9 lbs
- 44 lbs
- 22 lbs
- 6.6 lbs
11: When a refrigeration or air conditioning system is installed
- the form of certificate shall be authorized by the Department of Pubic safety
- it shall be approved by the owner for proper operation.
- it shall not be operated below prescribed pressures
- a field inspection shall be made before it is put into service
12: What section of ASHRAE-15 governs pressure vessels?
- Section 7 ASHRAE-15 ASME VIII fired
- Section 6 ASHRAE-34 ASME VIII unfired
- OSHA
- Section 9 ASHRAE-15 ASME VIII unfired
13: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
14: The certificate of inspection
- shall be authorized by a notarized insurance company
- shall be posted on the compressor shell or electrical panel at the unit
- shall be posted and protected from dirt, water, and other elements
- shall be $20 and an additional fee of $1 for each tone above 20 tons
15: A movie theater would be considered a
- institutional occupancy
- mixed occupancy
- public assembly occupancy
- commercial occupancy
16: Pressure relief valves shall be marked with the data from
- Section VIII Division of the ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section I Division VIII of ASME Boiler & Pressure Code
- Section XIII Division of the ASME Boiler & Pressure Code
17: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
18: Each machinery room shall contain
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- high and low pressure controls
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
19: Halogenated refrigerants cannot be used with what material?
- Stainless steel
- Magnesium alloy
- Aluminum
- Copper
20: How much refrigerant can be stored in a mechanical room outside of the system?
- 330
- 100
- 150
- 200
21: What must be done to all doors and access points in duct work going through a mechanical room?
- Must be hindged
- Must be screwed shut
- Must be sealed and gasketed
- All of the above
22: Liquid level gauge glasses shall have automatic closing shut off valves, except Bull's eye or reflex type.
- True
- False
23: B3 refrigerants are considered
- toxic and highly flammable
- non-toxic but flammable
- toxic but non-flammable
- non-toxic but non-flammable
24: Halo-carbon refrigerants cannot be used with what material?
- Stainless Steel
- Magnesium alloy
- Aluminum
- Copper
25: Doors communicating with outside from a mechanical room must be?
- Self-closing, approved, fire door
- Steel, approved, weather-stripped
- Self-closing, wooden, fire door
- Self-closing, aligned, fire door