ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: System design pressures must take into consideration, not only, pressures found during normal operation but also what?

  • When it's cold out
  • When there is a malfunction on the high side
  • When its warm out
  • All of the above

2: Pipe identification labels are required when the system contains more than

  • 65 lbs
  • 110 lbs
  • 120 lbs
  • 55 lbs

3: What is the intention of the word “should” as used in the code?

  • A mandatory requirement
  • A recommendation or advisory guideline
  • A technician’s choice of how it should be done
  • None of the Above

4: Refrigeration devices shall be equipped with a ____ to protect against unexpected pressure due to a malfunction or fire?

  • T&P device
  • Circuit Breaker
  • Temperature limiter device
  • Relief valve

5: All electrical work done on refrigeration systems must comply with

  • OSHA
  • Department of Energy
  • ASHREA-15 Section 9.2.1
  • NEC and Massachusetts Modifications

6: When an inspection is needed, how often must it be done?

  • annually
  • every 18 months
  • every 24 months
  • every 36 months

7: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?

  • Flush with R-11
  • Flush with RX-11
  • Flush with R-718
  • Flush with ammonia

8: When a pressure gauge is permanently installed on a system, it must be ___ times the design pressure of the system.

  • 1.2
  • 2.2
  • 1.5
  • 1

9: How are refrigerant blends classified?

  • Based on worst case fractionation
  • Based on best case Fractionation
  • Based on the oil used
  • Blends don't have to be classified

10: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant

  • shall be inspected by the Boiler of Inspectors bi-annually
  • shall have a pressure limiting device and a pressure relief valve installed
  • shall have a pressure limiting device installed on the high side of the system
  • does not require a pressure-limiting device

11: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.

  • the same
  • higher
  • lower
  • there is no Group B1 refrigerants

12: What pipe can not be used for refrigeration?

  • N
  • L
  • K
  • M

13: The main purpose of a refrigerant detector in a machinery room is to

  • inform there is a refrigerant leak int he system
  • detect toxins in the air caused by a refrigerant leak
  • to set off an alarm when there is refrigerant present inside the room
  • all of the above

14: What is the refrigerant chlorodifluoromethane?

  • R-22
  • R-12
  • R-134a
  • R-123

15: Who authorizes changes to the safety codes?

  • Person who pulled the permit
  • Board of Boilers
  • Contractor who last serviced the system.
  • Person in charge of the facility

16: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8

  • low side of the system
  • high side of the system
  • the liquid side of the system
  • the vapor side of the system

17: R-11 belongs to Group

  • B-3
  • A-2
  • B-1
  • A-1

18: What type of relief valve is used on low pressure centrifugal compressor systems?

  • Spring-loaded relief valve
  • Rupture disc
  • Purge relief
  • None of the above

19: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.

  • 80%
  • 100%
  • 90%
  • 75%

20: R-410A is classified as a ____ refrigerant on the safety matrix.

  • B-2
  • A-1
  • B-1
  • A-2

21: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of

  • the aggregate of the high side and low side
  • the low side
  • the high side
  • 2.5 times the design pressure

22: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.

  • 18
  • 10
  • 15
  • 24

23: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.

  • 50
  • 100
  • 350
  • 550

24: When a receiver is greater than 3 cubic feet but less than 10 cubic feed, what is the minimum relief device required?

  • fusible plug
  • relief valve
  • rupture disc
  • all of the above

25: Evaporators within 18" of a heating coil must be equipped with a

  • pressure relief device
  • zone valve
  • low limit control
  • high limit control