Topics: ASHRAE/CMR
1: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.
- Lithium bromide
- ammonia
- HCFC-123
- CFC-11
2: Pressure vessels shall be provided with ___________in accordance with Section VIII of the ASME Boiler & Pressure Vessel Code
- Pressure vessels need no type of protection as long as it is hydrostatically tested every three months
- over pressure protection as well as a temperature protection device
- over pressure protection
- over pressure protection and a rupture disc
3: A pressure relief should be located at least _______ from windows and doors.
- 20'
- 30'
- 15'
- 25'
4: Pipe identification labels are required when the system contains more than
- 65 lbs
- 120 lbs
- 110 lbs
- 55 lbs
5: Halo-carbon refrigerants cannot be used with what material?
- Copper
- Magnesium alloy
- Stainless Steel
- Aluminum
6: Direct systems using Group II refrigerants
- shall be allowed to be used for human comfort.
- shall be installed per instruction of the AHJ
- shall not be used for air condition for human comfort
- shall be installed in Class T machinery rooms
7: Pressure relief devices are marked with a ____________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- UL and UM
- UV or UR
- UL and UR
- UM or UL
8: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- shall have a pressure limiting device installed on the high side of the system
- does not require a pressure-limiting device
- shall have a pressure limiting device and a pressure relief valve installed
- shall be inspected by the Boiler of Inspectors bi-annually
9: Class T machine room
- shall have remote controls to stop the action of the refrigerant compressor
- shall have refrigerant leak detecting systems installed inside and outside the room
- shall include closets used for setting equipment
- has no flame producing apparatus permanently installed
10: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
11: A declaration test is needed when the system contains more than
- 110 lbs
- 120 lbs
- 55 lbs
- 65 lbs
12: What is a Category "M" fluid?
- Any fluid that exceeds 150 psig and has design temperatures over 366F
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
- A typical refrigerant used on newer air conditioning and heat pump systems
13: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
14: What refrigerant doesn't have to be classified?
- R-717
- R-134A
- R-718
- R-422A
15: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
16: Refrigerant piping crossing an open space that affords passageway in any building shall not be less than _____ feet above the floor unless piping is located against the ceiling.
- 7.25'
- 9.00'
- 8'4"
- 7.00'
17: A 3-cubic foot receiver must have what type of relief valve?
- fusible plug
- relief valve
- rupture device
- none of the above
18: Can you use Ammonia in industrial applications?
- No, never
- Yes, Under certain condidtions
- Yes, always
- When mixed with R-718
19: Which refrigerant class listed below is the most flammable?
- A2
- B2
- A3
- C3
20: What pipe can not be used for refrigeration?
- L
- M
- K
- N
21: What should not (and can not) be located between a pressure imposing device and a pressure-limiting device?
- Stop valve
- Foot valve
- Muffler
- Moisture indicator
22: R-22 is considered a(n)
- HFC
- HCFCH
- CFC
- HCFC
23: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Nothing must be done
- you can never change refrigerants
- Place sign, check for leaks, and insulate suction line
- Make sure its compatible, notify owner, and notify AHJ.
24: What is R-22?
- CCFCM
- Chlorofluoromethane
- Chlorodifluoromethane
- HFC
25: What would be the classification for Stop & Shop grocery store?
- Place of assembly
- Instituional
- Industrial
- Large mercantile