ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: When must refrigeration system covered by the code be inspected?

  • Upon installation
  • Not required
  • Annually and when installed
  • Annually

2: What pipe can not be used for refrigeration?

  • L
  • K
  • N
  • M

3: Ammonia (NH3) is a group III refrigerant

  • True
  • False

4: What is an example of institutional occupancy?

  • Dorms
  • Hospital
  • Football stadium
  • Shopping mall

5: Class 3 refrigerants are

  • highly flammable
  • toxic
  • non-flammable
  • non-toxic

6: Halo-carbon refrigerants cannot be used with what material?

  • Copper
  • Aluminum
  • Magnesium alloy
  • Stainless Steel

7: What is not a requirement of a class T machine room?

  • self-closing doors
  • fire hose connection to the building fire protection system
  • tight fitting doors
  • automatic ventilation

8: NH3 is

  • ammonia
  • R-508A
  • R-718
  • lithium bromide

9: When should a relief valve start to function?

  • 10 psi before it's set pressure
  • Before the purge station discharges
  • Two times it's working pressure
  • At it's set pressure

10: What would be the classification of a prison?

  • Place of assembly
  • Industrial
  • Institutional
  • Large mercantile

11: All machine rooms must be outfitted with a detector that _______?

  • activates an audible alarm
  • activates a visual alarm
  • starts the ventilation system
  • All of the above

12: Fusible plugs shall not be used with pressure vessels of

  • 3 cubic feet or less
  • 3 cubic feet or more
  • 15 square feet or less
  • 15 cubic feet or more

13: What refrigerant is an inorganic compound?

  • R-410A
  • R-22
  • Ammonia
  • R-132A

14: What section governs pressure vessels?

  • Section ASHREA 34
  • Section 8 ASHREA 15 ASME unfired
  • Section 1 ASHREA 15 ASME fired
  • OSHA

15: What type of refrigerants are NOT flammable?

  • CHC
  • HFC
  • HCFC
  • All of the above

16: Pressure relief valves shall be marked with the data from

  • Section XIII Division of the ASME Boiler & Pressure Code
  • Section I Division VIII of ASME Boiler & Pressure Code
  • Section IV Division of the ASME Boiler & Pressure Code
  • Section VIII Division of the ASME Boiler & Pressure Code

17: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.

  • True
  • False

18: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.

  • 50
  • 100
  • 550
  • 350

19: When a receiver is greater than 3 cubic feet but less than 10 cubic feed, what is the minimum relief device required?

  • fusible plug
  • relief valve
  • rupture disc
  • all of the above

20: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.

  • the return air ducted system
  • the outdoors
  • the mechanical room housing the refrigeration system
  • Machinery rooms need not be vented

21: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed

  • 55 lbs
  • 550 lbs
  • 330 lbs.
  • 660 lbs

22: What is the refrigerant dichlorodifluoromethane?

  • R-123
  • R-22
  • R-134A
  • R-12

23: What does safe access mean?

  • OSHA approved
  • Locked doors
  • A clear unobstructed path to the equipment and controls
  • Well-lit exit signs

24: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere

  • 330
  • 110
  • 6.6
  • 1,000

25: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by

  • District Engineering Inspectors
  • Commissioned Inspectors
  • Master licensed Technician
  • both a or b