ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: What refrigerant were phased out in 2004?

  • R-12
  • R-22
  • R-134a
  • R-11

2: A positive displacement compressor is

  • is a reciprocating type compressor with 2 or more pistons
  • a compressor in which the increase in pressure is attained by changing the internal pressure of the compression chamber
  • where the compressor's suction pressure and the compressor;s discharge pressure is more than 50 PSI
  • a compressor in which the increase in pressure is attained by changing the internal volume of the compression chamber

3: Pressure limiting devices are not required for systems containing less then ________ refrigerants.

  • 44 lbs
  • 13.9 lbs
  • 22 lbs
  • 6.6 lbs

4: Where a refrigeration or air conditioning system is installed,

  • The company who installed the system must notify the fire department in the jurisdiction where installed
  • it shall not be operated below prescribed pressuers
  • A field inspection shall be made before it is put into service
  • the form or certificate shall be authorized by the Department of Public Safety

5: Before you change the type of refrigerant in a refrigeration system, what three things must be done?

  • Place sign, check for leaks, and insulate suction line
  • you can never change refrigerants
  • Make sure its compatible, notify owner, and notify AHJ.
  • Nothing must be done

6: Relief valves are rated in

  • gallons of water per hour
  • gallons of water per minute
  • pounds of air per minute
  • pounds of air per hour

7: Refrigerant restricted in 2004 but used for transition for decades:

  • R-123
  • R-134A
  • R-22
  • R-11

8: The 522 CMR 9.00 has adopted for reference ASHRAE ____

  • 10
  • 15
  • III
  • 25

9: How many gallons of water per pound of ammonia do you need?

  • 1
  • 20
  • 15
  • 5

10: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants

  • there is no Group B1 refrigerants
  • the same
  • higher
  • lower

11: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by

  • District Engineering Inspectors
  • Commissioned Inspectors
  • Master licensed Technician
  • both a or b

12: High pressure controls should be set no higher than

  • 10% of set point
  • 90% of set point
  • 80% of set point
  • 25% of set point

13: Joints in piping for refrigeration containing parts must withstand temperatures of ___?

  • 700F
  • 1000F
  • 600F
  • 800F

14: Pressure vessels with an internal volume of 10 cubic feet or more

  • shall use fusible plugs
  • shall use pressure relief devices or fusible plugs
  • shall use pressure relief devices
  • shall use rupture discs or duel pressure relief valves

15: What is the intention of the word “shall” as used in the code?

  • A mandatory requirement
  • A recommendation or advisory guideline
  • A technician’s choice of how it should be done
  • None of the above

16: R-11 belongs to Group

  • B-3
  • A-2
  • B-1
  • A-1

17: A professional or office building would be considered what type of occupancy?

  • public assembly
  • mercantile
  • commercial
  • business

18: B3 refrigerants are considered

  • non-toxic but non-flammable
  • toxic but non-flammable
  • non-toxic but flammable
  • toxic and highly flammable

19: What is the minimum height refrigeration piping should be placed against walls?

  • 72"
  • Ceiling height
  • 7.25'
  • 6'

20: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.

  • 18
  • 10
  • 15
  • 24

21: What kind of material can't be used on the outlet of a relief valve?

  • PVC
  • Stainless Steel
  • Copper
  • Aluminum

22: Which of the following are considered inorganic refrigerants?

  • R-717 and R-718
  • 410A and R-407C
  • R-500 and R-502
  • None of the above

23: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the

  • load-side of the contactor in
  • first disconnect in
  • 24 volt secondary side of the Class 2 transformer to the thermostat
  • breaker panel in

24: R-718 is rated unlimited for refrigeration quantity contained in a system. Why?

  • Because it's water
  • Because it's cheap
  • R-718 is not rated unlimited because it's a dangerous refrigerant
  • Because it's a non-flammable refrigerant

25: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of

  • the ASME Boiler and Pressure Vessel Code
  • Section 11.3.1.5 ASHRAE 15 Standard
  • the ANSI Standard 10.7.2
  • both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5