Topics: ASHRAE/CMR
1: Where must a refrigeration contractor's license number be displayed?
- Uniforms, checks, and invoices.
- Truck, office, every job, and on all equipment
- Trucks, license plates, and uniforms
- Trucks, invoices, and advertising
2: Pressure relief devices are marked with a ____________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- UL and UM
- UM or UL
- UL and UR
- UV or UR
3: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.
- higher
- lower
- there is no Group B1 refrigerants
- the same
4: Pressure vessels with an internal volume of 3 cubic feet or less
- shall use fusible plugs
- shall use pressure relief devices
- do not need pressure relief protection
- shall use pressure relief devices or fusible plugs
5: What happens after your initial inspection of a pressure vessel?
- There is a temporary shut-down until a final inspection can be performed.
- Inspector leaves a metal tag with a certification listed on it
- Notify the AHJ to let them know that the system been inspected
- Notify the Fire Marshal that the system has been inspected and approved
6: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Make sure its compatible, notify owner, and notify AHJ.
- you can never change refrigerants
- Place sign, check for leaks, and insulate suction line
- Nothing must be done
7: What refrigerant were phased out in 2004?
- R-11
- R-12
- R-22
- R-134a
8: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with RX-11
- Flush with R-11
- Flush with ammonia
- Flush with R-718
9: R-123 belongs to Group
- B-3
- B-2
- A-3
- B-1
10: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 2.5, 3.0
- 3.0, 3.5
- 2.5, 2.5
- 6.6, 6.6
11: A relief valve discharge capacity is rated in
- Pounds of air per minute.
- PSIA
- temperature minus pounds of air per second divided by release rate squared
- PSIG
12: R-12. R-22, and R-40 are considered Group I refrigerants.
- True
- False
13: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When there is a space 6' or more above it
- When it's used as part of a supply or return air system
- When its white
- When there are sprinklers above
14: What is the minimum height refrigeration piping should be placed against walls?
- 72"
- 7.25'
- 6'
- Ceiling height
15: How many gallons of water do you need per pound of ammonia?
- 100
- 1
- 10
- 50
16: A class B2 refrigerant is considered
- toxic and non-flammable
- non-toxic and non-flammable
- toxic and somewhat flammable
- non-toxic and highly flammable
17: An example of direct system is
- rooftop unit
- chiller
- absorber
- none of the above
18: The Board of Boilers adopts by reference
- Montreal Protocol Safety Code
- the MACS Pressure Vessel Code of Massachusetts
- MSCA Code
- the 1997 ANSI/ASHRAE Safety Code
19: pressure relief valves must discharge to the atmosphere at a location not less than 15 feet from ground level and ____ feet from any window, ventilation opening, or exits of buildings.
- 10
- 15
- 25
- 20
20: A declaration test is needed when the system contains more than
- 65 lbs
- 110 lbs
- 120 lbs
- 55 lbs
21: Each machinery room shall contain
- high and low pressure controls
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
22: How far from the ground does a relief valve need to be?
- At least 25' above grade
- At least 15' above grade
- Not more than 3' above grade
- At least 20' above grade
23: What refrigerant doesn't have to be classified?
- R-422A
- R-718
- R-717
- R-134A
24: Where a refrigeration or air conditioning system is installed,
- A field inspection shall be made before it is put into service
- The company who installed the system must notify the fire department in the jurisdiction where installed
- it shall not be operated below prescribed pressuers
- the form or certificate shall be authorized by the Department of Public Safety
25: Class T machine room
- shall include closets used for setting equipment
- shall have remote controls to stop the action of the refrigerant compressor
- shall have refrigerant leak detecting systems installed inside and outside the room
- has no flame producing apparatus permanently installed