Topics: ASHRAE/CMR
1: What refrigerant doesn't have to be classified?
- R-717
- R-718
- R-422A
- R-134A
2: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
3: When air is ducted through a machine room that services occupied space, What must be done?
- Insulated and cross broke
- Welded and seamed.
- Ducted and sealed
- Flanged and gasketed
4: How far from the window does a relief valve need to be according to ASHRAE-15?
- There is no minimum for relief valve and windows.
- At least 40'
- At least 30'
- At least 20'
5: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
6: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Place sign, check for leaks, and insulate suction line
- you can never change refrigerants
- Make sure its compatible, notify owner, and notify AHJ.
- Nothing must be done
7: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- public assembly occupancy
- institutional occupancy
- mixed occupancy
- commercial occupancy
8: What pipe can not be used for refrigeration?
- K
- N
- L
- M
9: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
10: Ammonia (NH3) is a group III refrigerant
- True
- False
11: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- regularly
- annually
- bi-annually
- quarterly
12: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the
- breaker panel in
- first disconnect in
- load-side of the contactor in
- 24 volt secondary side of the Class 2 transformer to the thermostat
13: Pressure vessels having an inside diameter of 6” or less shall be protected by
- a fusible plug
- a pressure relief device
- either a fusible plug or a pressure relief device
- Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
14: What must be done to refrigerant pipes before being buried ?(8.10.4)
- Classifed
- Certified
- Leak checked
- Insulated and installed in a pipe duct (Encased)
15: What is a Category "M" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
- A typical refrigerant used on newer air conditioning and heat pump systems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
- Any fluid that exceeds 150 psig and has design temperatures over 366F
16: The certificate of inspection
- shall be authorized by a notarized insurance company
- shall be posted and protected from dirt, water, and other elements
- shall be $20 and an additional fee of $1 for each tone above 20 tons
- shall be posted on the compressor shell or electrical panel at the unit
17: R-22 is considered a(n)
- HCFC
- HCFCH
- HFC
- CFC
18: The Board of Boilers adopts by reference
- the 1997 ANSI/ASHRAE Safety Code
- MSCA Code
- Montreal Protocol Safety Code
- the MACS Pressure Vessel Code of Massachusetts
19: How many gallons of water per pound of ammonia do you need?
- 15
- 5
- 20
- 1
20: Pressure relief valves shall be marked with the data from
- Section XIII Division of the ASME Boiler & Pressure Code
- Section I Division VIII of ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
21: Direct systems using Group II refrigerants
- shall be installed in Class T machinery rooms
- shall not be used for air condition for human comfort
- shall be installed per instruction of the AHJ
- shall be allowed to be used for human comfort.
22: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
23: Machinery rooms must be vented to ______?
- neutralizing tank
- unoccupied spaces
- basement
- outdoors
24: Pipe identification labels are required when the system contains more than
- 120 lbs
- 65 lbs
- 110 lbs
- 55 lbs
25: A hotel is considered a _______ occupancy.
- institutional
- residential
- mercantile
- commercial