Topics: ASHRAE/CMR
1: Walls and doors of a machinery room shall be at least _____ hour(s) fire rated.
- 5
- 3
- 2
- 1
2: When a refrigerating machinery room is used, the emergency procedures shall be posted
- on a conspicuous card located near the compressor
- inside the room, immediately adjacent to each door
- outside the room, immediately adjacent to each door
- on a conspicuous card located near the evaporator
3: What would be the classification of a church?
- Industrial
- Large mercantile
- Place of assembly
- Institutional
4: Most CFC's are
- inert but toxic
- inert
- flammable
- toxic
5: A relief valve discharge capacity is rated in
- PSIG
- temperature minus pounds of air per second divided by release rate squared
- Pounds of air per minute.
- PSIA
6: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
7: What is not a requirement of a Class T machine room?
- Fire hose connected to the building fire protection system.
- Tight fitting doors
- Automatic ventilation
- Self-closing doors
8: What happens after your initial inspection of a pressure vessel?
- Notify the AHJ to let them know that the system been inspected
- Inspector leaves a metal tag with a certification listed on it
- Notify the Fire Marshal that the system has been inspected and approved
- There is a temporary shut-down until a final inspection can be performed.
9: The Board of Boilers adopts by reference
- the 1997 ANSI/ASHRAE Safety Code
- the MACS Pressure Vessel Code of Massachusetts
- MSCA Code
- Montreal Protocol Safety Code
10: Which refrigerant was still able to be vented to the atmosphere after July 1, 1992?
- R-12
- R-11
- R-113
- R-22
11: R-22 is classified as a ____ refrigerant on the safety matrix.
- A-2
- B-1
- B-2
- A-1
12: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When it's used as part of a supply or return air system
- When there is a space 6' or more above it
- When there are sprinklers above
- When its white
13: What section governs pressure vessels?
- Section 1 ASHREA 15 ASME fired
- Section ASHREA 34
- OSHA
- Section 8 ASHREA 15 ASME unfired
14: The main cause of enacting the "no vending rule" of July 1st 1992 was
- global warming potential
- ozone depletion
- both a & b
- None of the above
15: A 3-cubic foot receiver must have what type of relief valve?
- fusible plug
- relief valve
- rupture device
- none of the above
16: Indirect systems using Group II refrigerants
- shall be used for mechanical equipment only
- shall be used in refrigeration system less than 1,000 lbs
- shall have all refrigerant containing parts except piping, installed in a Class T machine room
- shall be used in refrigeration system in excess of 1,000 lbs
17: A High-Probability System
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
18: Direct systems using Group II refrigerants
- shall be installed in Class T machinery rooms
- shall be installed per instruction of the AHJ
- shall be allowed to be used for human comfort.
- shall not be used for air condition for human comfort
19: Which refrigerant(s) is an HFC?
- R-22
- R-410A
- R-502
- All of the above
20: A positive displacement compressor is
- a compressor in which the increase in pressure is attained by changing the internal pressure of the compression chamber
- a compressor in which the increase in pressure is attained by changing the internal volume of the compression chamber
- is a reciprocating type compressor with 2 or more pistons
- where the compressor's suction pressure and the compressor;s discharge pressure is more than 50 PSI
21: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
22: The color code of a tank of ammonia is
- light green
- lavender
- silver
- white
23: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with ammonia
- Flush with R-718
- Flush with RX-11
- Flush with R-11
24: A class B2 refrigerant is considered
- toxic and somewhat flammable
- non-toxic and non-flammable
- non-toxic and highly flammable
- toxic and non-flammable
25: R-717 is
- water
- ammonia
- carbon dioxide
- trichloromethane