ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: Stop valves shall not be permitted between the system and the

  • service valve
  • condenser
  • bleed valve
  • relief valve

2: Joints in piping for refrigeration containing parts must withstand temperatures of ___?

  • 700F
  • 1000F
  • 600F
  • 800F

3: What is the refrigerant chlorodifluoromethane?

  • R-22
  • R-12
  • R-134a
  • R-123

4: High pressure controls should be set no higher than

  • 10% of set point
  • 90% of set point
  • 80% of set point
  • 25% of set point

5: A class B1 refrigerant is considered

  • toxic and somewhat flammable
  • non-toxic and non-flammable
  • toxic but non-flammable
  • non-toxic but highly flammable

6: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.

  • True
  • False

7: R-22 falls under which safety classification?

  • B-1
  • A-2
  • B-2
  • A-1

8: NH3 is

  • R-508A
  • ammonia
  • lithium bromide
  • R-718

9: R-410A is classified as a ____ refrigerant on the safety matrix.

  • B-2
  • A-1
  • B-1
  • A-2

10: Class 3 refrigerants are

  • toxic
  • non-flammable
  • highly flammable
  • non-toxic

11: What is not a requirement of a class T machine room?

  • fire hose connection to the building fire protection system
  • tight fitting doors
  • automatic ventilation
  • self-closing doors

12: Single compound Refrigerants are classified by what two criteria?

  • Flammability and temperature range
  • Flammability and toxicity
  • Weight and color
  • Temperature range and hazardousness

13: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed

  • 660 lbs
  • 55 lbs
  • 330 lbs.
  • 550 lbs

14: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?

  • phosgene gas sening
  • CO Sensing
  • A group sensing
  • refrigerant sensing

15: Ammonia can come in contact with _______ ?

  • Aluminum
  • Brass
  • Copper
  • Copper tubing

16: A room having machinery but no flame producing apparatus permanently installed and operated is considered a

  • Class A machinery room
  • Class B machinery room
  • Class T machinery room
  • Class M machinery room

17: Refrigerant restricted in 2004 but used for transition for decades:

  • R-123
  • R-134A
  • R-22
  • R-11

18: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.

  • ammonia
  • CFC-11
  • Lithium bromide
  • HCFC-123

19: Direct systems using Group II refrigerants

  • shall be installed per instruction of the AHJ
  • shall not be used for air condition for human comfort
  • shall be allowed to be used for human comfort.
  • shall be installed in Class T machinery rooms

20: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.

  • 50
  • 100
  • 350
  • 550

21: All machine rooms must be outfitted with a detector that _______?

  • activates an audible alarm
  • activates a visual alarm
  • starts the ventilation system
  • All of the above

22: Before you change the type of refrigerant in a refrigeration system, what three things must be done?

  • Place sign, check for leaks, and insulate suction line
  • you can never change refrigerants
  • Make sure its compatible, notify owner, and notify AHJ.
  • Nothing must be done

23: What type of relief valve is used on a CO2 system?

  • fusible plug
  • rupture disc
  • glove disc
  • gate valve

24: What type of copper is not permitted on refrigeration systems?

  • Type M
  • Type K
  • Type N
  • Type L

25: Pressure vessels with an internal volume of 3 cubic feet or less

  • shall use pressure relief devices
  • shall use fusible plugs
  • shall use pressure relief devices or fusible plugs
  • do not need pressure relief protection