Topics: ASHRAE/CMR
1: Fusible plugs shall not be used with pressure vessels of
- 15 cubic feet or more
- 3 cubic feet or less
- 3 cubic feet or more
- 15 square feet or less
2: How many flammability classifications are refrigerants in?
- 7
- 3
- 5
- 2
3: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 6.6
- 110
- 330
- 1,000
4: How many groups of refrigerants are there?
- 7
- 1
- 5
- 3
5: Pressure vessels with an internal volume of 10 cubic feet or more
- shall use fusible plugs
- shall use pressure relief devices or fusible plugs
- shall use pressure relief devices
- shall use rupture discs or duel pressure relief valves
6: How many refrigerant classifications are there for flammability?
- 7
- 2
- 1
- 3
7: All electrical work done on refrigeration systems must comply with
- OSHA
- Department of Energy
- ASHREA-15 Section 9.2.1
- NEC and Massachusetts Modifications
8: When releasing a hydrogenated hydrocarbon refrigerant to the atmosphere, ample ventilation must be provided and
- no flames shall be permitted
- gas masks must be worn
- the owner shall be informed
- explosion precautions must be taken
9: What section of ASHRAE-15 governs pressure vessels?
- Section 6 ASHRAE-34 ASME VIII unfired
- OSHA
- Section 7 ASHRAE-15 ASME VIII fired
- Section 9 ASHRAE-15 ASME VIII unfired
10: What must be done to all doors and access points in duct work going through a mechanical room?
- Must be hindged
- Must be screwed shut
- Must be sealed and gasketed
- All of the above
11: Relief valves are rated in
- gallons of water per hour
- gallons of water per minute
- pounds of air per minute
- pounds of air per hour
12: What kind of material can't be used on the outlet of a relief valve?
- PVC
- Stainless Steel
- Copper
- Aluminum
13: A professional or office building would be considered what type of occupancy?
- public assembly
- mercantile
- commercial
- business
14: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- high side of the system
- the liquid side of the system
- the vapor side of the system
15: Halogenated refrigerants cannot be used with what material?
- Stainless steel
- Aluminum
- Magnesium alloy
- Copper
16: How much clearance do you need around the perimeter of electrical panels?
- 12"
- 36"
- 24"
- 18"
17: Which refrigerant replaced R-12?
- R-22
- R-407A
- R-410A
- R-134A
18: What is the refrigerant chlorodifluoromethane?
- R-22
- R-12
- R-134a
- R-123
19: How much refrigerant can be stored in a mechanical room outside of the system?
- 200
- 150
- 330
- 100
20: Doors communicating with outside from a mechanical room must be?
- Self-closing, aligned, fire door
- Self-closing, approved, fire door
- Self-closing, wooden, fire door
- Steel, approved, weather-stripped
21: What refrigerant doesn't have to be classified?
- R-134A
- R-422A
- R-718
- R-717
22: Joints in refrigeration piping must be _____ before being covered?
- Pressurized
- Insulated
- Inspected
- Leak tested
23: What would be the classification of a church?
- Industrial
- Institutional
- Place of assembly
- Large mercantile
24: Who authorizes the form of certificate of completion of refrigeration systems that should be used?
- Massachusetts Board of Boiler Rules
- Owner
- Fire Marshal
- Supervisor or project manager in charge of the installation
25: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.
- 100
- 80
- 110
- 90