Topics: ASHRAE/CMR
1: A declaration test is needed when the system contains more than
- 120 lbs
- 55 lbs
- 65 lbs
- 110 lbs
2: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
3: Where are the three places that the discharge from an ammonia relief valve be piped?
- To chemical neutralizing tank only
- Underground, into drain, into mechanical room
- Atmosphere, Tank containing water, where the AHJ indicates.
- None of the above.
4: Relief valves are rated in
- gallons of water per hour
- gallons of water per minute
- pounds of air per minute
- pounds of air per hour
5: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
6: When releasing a hydrogenated hydrocarbon refrigerant to the atmosphere, ample ventilation must be provided and
- gas masks must be worn
- explosion precautions must be taken
- the owner shall be informed
- no flames shall be permitted
7: What must be done to refrigerant pipes before being buried?
- Coated
- Certified
- Encased
- Leaked checked
8: Pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 22
- 50
- 18
- 33
9: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
10: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with ammonia
- Flush with RX-11
- Flush with R-718
- Flush with R-11
11: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
12: R-717 is
- trichloromethane
- carbon dioxide
- water
- ammonia
13: Which refrigerant was still able to be vented to the atmosphere after July 1, 1992?
- R-22
- R-11
- R-113
- R-12
14: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 1,000
- 10,000
- 100
- 100,000
15: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the
- load-side of the contactor in
- 24 volt secondary side of the Class 2 transformer to the thermostat
- first disconnect in
- breaker panel in
16: How far from the window does a relief valve need to be according to ASHRAE-15?
- There is no minimum for relief valve and windows.
- At least 40'
- At least 20'
- At least 30'
17: Which occupancy can ammonia be used in?
- commercial
- depends on the quantity of freon
- industrial
- redifential
18: What would be the classification for Stop & Shop grocery store?
- Large mercantile
- Place of assembly
- Instituional
- Industrial
19: Large Mercantile occupancy is a premise or that portion of a premise where more than ____ persons congregate on levels above or below the street level to purchase personal merchandise.
- 100
- 400
- 250
- 350
20: What type of relief valve is used on low pressure centrifugal compressor systems?
- Spring-loaded relief valve
- Rupture disc
- Purge relief
- None of the above
21: What is a Category "D" fluid?
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
- Any fluid that exceeds 150 psig and has design temperature of over 366F
22: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
23: What type of material can't be used on the outlet of a relief valve?
- Copper
- Stainless steel
- PVC
- Magnesium alloy
24: Setting a pressure relief device shall not exceed ___ of the design pressure
- 80%
- 90%
- 75%
- 100%
25: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.
- containing R-11, R-123 & R-717 exclusively shall not be prohibited
- shall not be prohibited
- of Group B2 refrigerant shall be prohibited
- shall be prohibited