Topics: ASHRAE/CMR
1: What refrigerant doesn't have to be classified?
- R-717
- R-422A
- R-718
- R-134A
2: How many CFMs are required per square foot of commercial office occupied space
- .5 CFM
- 20 CFM
- 5 CFM
- 15 CFM
3: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- commercial occupancy
- institutional occupancy
- public assembly occupancy
- mixed occupancy
4: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
5: Trichlorofluoromethane is the name of what refrigerant?
- R-502
- R-11
- R-113
- R-12
6: A Low-Probability System
- is a system highly likely to leak form a failed connection or component of such system
- is such that a leak of refrigerant from a failed connection can not enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
7: Pressure limiting devices are not required for systems containing less then ________ refrigerants.
- 6.6 lbs
- 44 lbs
- 13.9 lbs
- 22 lbs
8: A High-Probability System
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
9: Machinery rooms must be vented to ______?
- basement
- neutralizing tank
- unoccupied spaces
- outdoors
10: All serviceable components of a refrigeration system shall be provided with
- manufactures instructions on start-up procedures
- service manuals
- name plates with markings referring to pressure and temperature in accordance with ASME Boiler and Pressure Vessel Code
- safe access
11: Which refrigerant(s) is an HFC?
- R-22
- R-410A
- R-502
- All of the above
12: Each machinery room shall contain
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- high and low pressure controls
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
13: A movie theater would be considered a
- commercial occupancy
- mixed occupancy
- public assembly occupancy
- institutional occupancy
14: How are refrigerant blends classified?
- Based on the oil used
- Based on best case Fractionation
- Based on worst case fractionation
- Blends don't have to be classified
15: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
16: Ammonia belongs to Group
- A-2
- A-1
- B-1
- B-2
17: The 522 CMR 9.00 has adopted for reference ASHRAE ____
- 25
- 10
- 15
- III
18: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
19: Ammonia is under what safety classification?
- B1
- A3
- B3
- B2
20: What is an example of institutional occupancy?
- Football stadium
- Dorms
- Hospital
- Shopping mall
21: An example of direct system is
- rooftop unit
- chiller
- absorber
- none of the above
22: Pressure vessel having an inside diameter exceeding 6” with an internal pressure greater than 15psig shall be marked directly on or on the nameplate the letters _______________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- “UL”
- “UV”
- “U” or “UM”
- “UM” and “UV”
23: How far from the window does a relief valve need to be according to ASHRAE-15?
- At least 40'
- At least 20'
- There is no minimum for relief valve and windows.
- At least 30'
24: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.
- containing R-11, R-123 & R-717 exclusively shall not be prohibited
- of Group B2 refrigerant shall be prohibited
- shall be prohibited
- shall not be prohibited
25: Low temperature systems should have what?
- High pour point
- Low pour point
- High viscosity
- None of the above