Topics: ASHRAE/CMR
1: What is an example of institutional occupancy?
- Dorms
- Shopping mall
- Football stadium
- Hospital
2: Pressure relief valves shall be marked with the data from
- Section I Division VIII of ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section XIII Division of the ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
3: A professional or office building would be considered what type of occupancy?
- mercantile
- public assembly
- commercial
- business
4: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Make sure its compatible, notify owner, and notify AHJ.
- Nothing must be done
- you can never change refrigerants
- Place sign, check for leaks, and insulate suction line
5: When air is ducted through a machine room that services occupied space, What must be done?
- Insulated and cross broke
- Ducted and sealed
- Flanged and gasketed
- Welded and seamed.
6: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- commercial occupancy
- mixed occupancy
- institutional occupancy
- public assembly occupancy
7: Where a refrigeration or air conditioning system is installed,
- A field inspection shall be made before it is put into service
- the form or certificate shall be authorized by the Department of Public Safety
- The company who installed the system must notify the fire department in the jurisdiction where installed
- it shall not be operated below prescribed pressuers
8: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.
- 15
- 20
- 50
- 75
9: What type of copper is not permitted on refrigeration systems?
- Type M
- Type N
- Type L
- Type K
10: R-22 is classified as a ____ refrigerant on the safety matrix.
- B-1
- A-1
- B-2
- A-2
11: What is R-22?
- Chlorodifluoromethane
- HFC
- CCFCM
- Chlorofluoromethane
12: Doors communicating with outside from a mechanical room must be?
- Self-closing, aligned, fire door
- Steel, approved, weather-stripped
- Self-closing, approved, fire door
- Self-closing, wooden, fire door
13: Who authorizes changes to the safety codes?
- Contractor who last serviced the system.
- Board of Boilers
- Person who pulled the permit
- Person in charge of the facility
14: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 550 lbs
- 55 lbs
- 330 lbs.
- 660 lbs
15: Stop valves shall not be permitted between the system and the
- service valve
- bleed valve
- condenser
- relief valve
16: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
- outside the machinery room
- compressor
- boiler
- evaporator
17: A hotel is considered a _______ occupancy.
- mercantile
- institutional
- residential
- commercial
18: The Department that certifies the transportation of refrigerant is the
- DOT
- RSES
- EPA
- EPO
19: What is R-611’s ASHRAE Safety Code?
- C3
- B3
- B2
- A2
20: R-717 is
- ammonia
- trichloromethane
- carbon dioxide
- water
21: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of
- 2.5 times the design pressure
- the high side
- the aggregate of the high side and low side
- the low side
22: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
23: Ammonia can come in contact with _______ ?
- Copper
- Brass
- Aluminum
- Copper tubing
24: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
25: Name a CFC refrigerant(s):
- R-11
- R-12
- R-123
- both a & b