Topics: ASHRAE/CMR
1: What is Trichlorotrifluoromethane?
- R-11
- R-113
- R-13
- R-12
2: A class B1 refrigerant is considered
- toxic but non-flammable
- non-toxic but highly flammable
- non-toxic and non-flammable
- toxic and somewhat flammable
3: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- commercial occupancy
- mixed occupancy
- institutional occupancy
- public assembly occupancy
4: When this is installed on the high side of a system, it must be capable of reading 1.2 times the design pressure (ASHRAE 15 9.11.3)
- Pressure gauge
- Temperature gauge
- Sight glass gauge
- All of the above
5: Can ammonia be used on domestic system?
- yes
- no
- no, unless there is proper ventilation system installed
- yes, for systems under 10 tons
6: Halogen refrigerants are corrosive to which type of metal?
- black iron
- copper
- stainless steel
- magnesium
7: Can you use Ammonia in industrial applications?
- Yes, always
- Yes, Under certain condidtions
- No, never
- When mixed with R-718
8: What type of relief valve is used on low pressure centrifugal compressor systems?
- Spring-loaded relief valve
- Rupture disc
- Purge relief
- None of the above
9: Pressure vessel having an inside diameter exceeding 6” with an internal pressure greater than 15psig shall be marked directly on or on the nameplate the letters _______________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- “UM” and “UV”
- “UL”
- “U” or “UM”
- “UV”
10: Pressure vessels with an internal volume of 3 cubic feet or less
- shall use pressure relief devices or fusible plugs
- shall use pressure relief devices
- do not need pressure relief protection
- shall use fusible plugs
11: What kind of material can't be used on the outlet of a relief valve?
- PVC
- Stainless Steel
- Aluminum
- Copper
12: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
13: No open flames are allowed in the machinery room unless?
- Approved by the installing contractor
- Never can be allowed
- Only when combustion air is provided from outside of the machinery room
- Approved by the authorized person
14: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
15: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.
- 36
- 48
- 24
- 18
16: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- nothing must be done
- make sure it's compatible, notify owner, notify A.H.J
- place sign, check for leaks, insulate
- you can't change refrigerants
17: What refrigerant doesn't have to be classified?
- R-422A
- R-134A
- R-717
- R-718
18: What is a Category "M" fluid?
- Any fluid that exceeds 150 psig and has design temperatures over 366F
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
- A typical refrigerant used on newer air conditioning and heat pump systems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
19: Which refrigerant was still able to be vented to the atmosphere after July 1, 1992?
- R-11
- R-113
- R-12
- R-22
20: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- the outdoors
- Machinery rooms need not be vented
- the return air ducted system
- the mechanical room housing the refrigeration system
21: Pressure limiting devices are not required for systems containing less then ________ refrigerants.
- 44 lbs
- 22 lbs
- 13.9 lbs
- 6.6 lbs
22: Relief valves are rated in
- gallons of water per hour
- pounds of air per minute
- gallons of water per minute
- pounds of air per hour
23: What is the minimum height refrigeration piping should be placed against walls?
- 6'
- Ceiling height
- 72"
- 7.25'
24: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 550
- 350
- 100
25: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 55 lbs
- 500 lbs
- 660 lbs
- 330 lbs