Topics: ASHRAE/CMR
1: Pressure vessels with an internal volume of 3 cubic feet or more
- do not need pressure relief protection
- shall use pressure relief devices or fusible plugs
- shall use pressure relief devices
- shall use fusible plugs
2: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When it's used as part of a supply or return air system
- When its white
- When there is a space 6' or more above it
- When there are sprinklers above
3: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- shall have a pressure limiting device and a pressure relief valve installed
- shall be inspected by the Boiler of Inspectors bi-annually
- shall have a pressure limiting device installed on the high side of the system
- does not require a pressure-limiting device
4: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
5: What is a Category "M" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
- Any fluid that exceeds 150 psig and has design temperatures over 366F
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
- A typical refrigerant used on newer air conditioning and heat pump systems
6: A professional or office building would be considered what type of occupancy?
- commercial
- public assembly
- mercantile
- business
7: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 500 lbs
- 660 lbs
- 55 lbs
- 330 lbs
8: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.
- 75%
- 80%
- 100%
- 90%
9: When is the only time you can leave a service container attached to a system?
- Leaking system
- Recovery
- Charging
- Both b and c
10: What type of copper is not permitted on refrigeration systems?
- Type M
- Type L
- Type N
- Type K
11: Fusible plugs must have what marked on them?
- Melting temperature in F
- Melting temperature in C
- Opening pressure
- All of the above
12: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- the outdoors
- the return air ducted system
- the mechanical room housing the refrigeration system
- Machinery rooms need not be vented
13: According to ASHRAE Standard-15 9.8 Positive Displacement Compressor Protection, the pressure-relief device discharge into
- the low-pressure side of the system
- the high side of the system
- the liquid receiver
- both a and c are correct
14: Ammonia can come in contact with _______ ?
- Brass
- Aluminum
- Copper tubing
- Copper
15: R-717 is
- carbon dioxide
- trichloromethane
- ammonia
- water
16: How many refrigerant classifications are there for flammability?
- 3
- 2
- 7
- 1
17: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within
- 1 week
- 30 days
- 2 months
- 14 days
18: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
19: Large mercantile occupancy is
- a premise or that portion of a premise where more than 1500 persons congregate on levels above or below street level to purchase personal merchandise
- a premise or that portion of a premise where more than 200 persons congregate on levels above or below street level to purchase personal merchandise
- a premise of that portion of a premise where more than 100 persons congregate on levels above of below street level to purchase personal merchandise.
- a premise of that portion of a premise where more than 50 persons congregate on levels above of below street level to purchase personal merchandise.
20: The Board of Boilers adopts by reference
- Montreal Protocol Safety Code
- the MACS Pressure Vessel Code of Massachusetts
- the 1997 ANSI/ASHRAE Safety Code
- MSCA Code
21: Dual-pressure relief devices should be installed on
- vessels of 10 cubic feet or less
- vessels of 10 cubic feet or more
- vessels of 3 cubic feet or more
- vessels of 3 cubic feet or less
22: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
- boiler
- outside the machinery room
- compressor
- evaporator
23: What refrigerant doesn't have to be classified?
- R-717
- R-422A
- R-134A
- R-718
24: What does safe access mean?
- A clear unobstructed path to the equipment and controls
- Locked doors
- OSHA approved
- Well-lit exit signs
25: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.
- 50
- 15
- 20
- 75