Topics: ASHRAE/CMR
1: How much clearance do you need around the perimeter of electrical panels?
- 24"
- 18"
- 36"
- 12"
2: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
3: Name three things that must be done when changing refrigeration lubricant?
- You can't change lubricants.
- Make sure it's compatible, notify owner, notify AHJ
- Nothing must be done
- Place sign, check for leaks, insulate
4: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 100
- 550
- 350
5: How many CFMs are required per square foot of commercial office occupied space
- 20 CFM
- 15 CFM
- 5 CFM
- .5 CFM
6: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.
- 80%
- 100%
- 90%
- 75%
7: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 1,000
- 10,000
- 100,000
- 100
8: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
9: What is an example of institutional occupancy?
- Dorms
- Hospital
- Football stadium
- Shopping mall
10: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of
- the aggregate of the high side and low side
- the low side
- 2.5 times the design pressure
- the high side
11: Most CFC's are
- flammable
- inert but toxic
- toxic
- inert
12: Institutional occupancy is
- a premise or that portion of a premise where large numbers of people congregate and from which occupants cannot quickly vacate the space.
- a premise or that portion of a premise from which, because they are disabled, debilitated, or confined, occupants cannot readily leave without the assistance of others.
- a premise or that portion of a premise where people transact business, receive personal service, or purchase food and other goods.
- None of the above
13: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
14: What refrigerant doesn't have to be classified?
- R-717
- R-422A
- R-134A
- R-718
15: Pressure vessels shall be provided with ___________in accordance with Section VIII of the ASME Boiler & Pressure Vessel Code
- Pressure vessels need no type of protection as long as it is hydrostatically tested every three months
- over pressure protection as well as a temperature protection device
- over pressure protection
- over pressure protection and a rupture disc
16: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- shall have a pressure limiting device and a pressure relief valve installed
- does not require a pressure-limiting device
- shall have a pressure limiting device installed on the high side of the system
- shall be inspected by the Boiler of Inspectors bi-annually
17: What is not a requirement of a class T machine room?
- self-closing doors
- fire hose connection to the building fire protection system
- tight fitting doors
- automatic ventilation
18: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- licensed welder
- competent welder
- welder qualified
- licensed technician
19: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
20: What is the refrigerant dichlorodifluoromethane?
- R-123
- R-22
- R-134A
- R-12
21: Class A refrigerants are considered
- toxic
- non-toxic
- non-flammable
- flammable
22: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered
- commercial occupancy
- institutional occupancy
- public assembly occupancy
- mixed occupancy
23: Direct systems using Group II refrigerants
- shall be installed per instruction of the AHJ
- shall be installed in Class T machinery rooms
- shall be allowed to be used for human comfort.
- shall not be used for air condition for human comfort
24: Setting a pressure relief device shall not exceed ___ of the design pressure
- 100%
- 80%
- 75%
- 90%
25: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- regularly
- quarterly
- annually
- bi-annually