Topics: ASHRAE/CMR
1: Can you use Ammonia in industrial applications?
- No, never
- Yes, Under certain condidtions
- Yes, always
- When mixed with R-718
2: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
- 24
- 10
- 18
- 15
3: Where are the three places that the discharge from an ammonia relief valve be piped?
- To chemical neutralizing tank only
- Underground, into drain, into mechanical room
- Atmosphere, Tank containing water, where the AHJ indicates.
- None of the above.
4: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.
- of Group B2 refrigerant shall be prohibited
- shall not be prohibited
- shall be prohibited
- containing R-11, R-123 & R-717 exclusively shall not be prohibited
5: What would be the classification of a prison?
- Large mercantile
- Industrial
- Institutional
- Place of assembly
6: Refrigeration devices shall be equipped with a ____ to protect against unexpected pressure due to a malfunction or fire?
- Temperature limiter device
- Relief valve
- T&P device
- Circuit Breaker
7: What is the definition of exit?
- Anywhere where a stairwell leads to outdoors
- The separated fire-resistant portion of a means of egress providing a protected travel path between the exit access and the exit discharge
- Any doorway or pathway unobstructed for access to anywhere considered safe
- Both a & b
8: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.
- 80%
- 90%
- 75%
- 100%
9: Pressure vessels with an internal volume of 3 cubic feet or less
- do not need pressure relief protection
- shall use pressure relief devices or fusible plugs
- shall use fusible plugs
- shall use pressure relief devices
10: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
11: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
12: R-11 belongs to Group
- A-1
- B-3
- B-1
- A-2
13: What is not a requirement of a class T machine room?
- tight fitting doors
- fire hose connection to the building fire protection system
- self-closing doors
- automatic ventilation
14: R-22 is considered a(n)
- HFC
- HCFCH
- CFC
- HCFC
15: What is not a requirement of a Class T machine room?
- Fire hose connected to the building fire protection system.
- Automatic ventilation
- Self-closing doors
- Tight fitting doors
16: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.
- Lithium bromide
- ammonia
- HCFC-123
- CFC-11
17: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
18: Stop valves shall not be permitted between the system and the
- service valve
- bleed valve
- relief valve
- condenser
19: A hotel is considered a _______ occupancy.
- institutional
- commercial
- residential
- mercantile
20: The certificate of inspection
- shall be posted and protected from dirt, water, and other elements
- shall be $20 and an additional fee of $1 for each tone above 20 tons
- shall be posted on the compressor shell or electrical panel at the unit
- shall be authorized by a notarized insurance company
21: R-12. R-22, and R-40 are considered Group I refrigerants.
- True
- False
22: Halo-carbon refrigerants cannot be used with what material?
- Copper
- Magnesium alloy
- Stainless Steel
- Aluminum
23: What do you need to do when you install a new system?
- Document the superheat and subcooling reading
- Insulate the suction line before you take a superheat reading
- Add refrigerant
- Have it inspected
24: R-717 is
- trichloromethane
- ammonia
- water
- carbon dioxide
25: Ammonia is under what safety classification?
- B3
- B2
- B1
- A3