Topics: ASHRAE/CMR
1: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
2: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 500 lbs
- 660 lbs
- 55 lbs
- 330 lbs
3: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
4: Name an HCFC refrigerant(s):
- R-22
- R-123
- R-11
- both a & b
5: Liquid level gauge glasses shall have automatic closing shut off valves, except Bull's eye or reflex type.
- True
- False
6: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- welder qualified
- licensed technician
- licensed welder
- competent welder
7: No open flames are allowed in the machinery room unless?
- Approved by the authorized person
- Only when combustion air is provided from outside of the machinery room
- Never can be allowed
- Approved by the installing contractor
8: What is an egress?
- An escape route
- A valve put on the low side of the system to prevent frosting
- An entrance or exit
- A code violation
9: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
10: What type of relief valve is used on low pressure centrifugal compressor systems?
- Spring-loaded relief valve
- Rupture disc
- Purge relief
- None of the above
11: What refrigerant has zero ozone depletion
- HFC
- CFC
- HCFC
- None of the above
12: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
13: When a refrigerating machinery room is used, the emergency procedures shall be posted
- outside the room, immediately adjacent to each door
- inside the room, immediately adjacent to each door
- on a conspicuous card located near the compressor
- on a conspicuous card located near the evaporator
14: Name a CFC refrigerant(s):
- R-11
- R-12
- R-123
- both a & b
15: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 1,000
- 100
- 10,000
- 100,000
16: A class A3 refrigerant is considered
- toxic and non-flammable
- toxic and somewhat flammable
- non-toxic and non-flammable
- non-toxic but highly flammable
17: What would be the classification of a church?
- Large mercantile
- Institutional
- Industrial
- Place of assembly
18: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
19: R-717 is
- ammonia
- carbon dioxide
- trichloromethane
- water
20: Which refrigerant replaced R-12?
- R-134A
- R-22
- R-410A
- R-407A
21: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.
- HCFC-123
- CFC-11
- Lithium bromide
- ammonia
22: B3 refrigerants are considered
- non-toxic but non-flammable
- toxic but non-flammable
- toxic and highly flammable
- non-toxic but flammable
23: How far from the window does a relief valve need to be according to ASHRAE-15?
- There is no minimum for relief valve and windows.
- At least 20'
- At least 30'
- At least 40'
24: There can be no airflow from an occupied space through a machine room unless what?
- System is high velocity
- System is ducted and sealed
- Duct is not located in the ceiling
- None of the above.
25: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 6.6, 6.6
- 3.0, 3.5
- 2.5, 3.0
- 2.5, 2.5