Topics: ASHRAE/CMR
1: _____ and its alloys are suitable for use with ammonia systems.
- Magnesium
- Copper
- Zinc
- Aluminum
2: What should not (and can not) be located between a pressure imposing device and a pressure-limiting device?
- Foot valve
- Muffler
- Moisture indicator
- Stop valve
3: R-22 is considered a(n)
- HCFC
- CFC
- HCFCH
- HFC
4: Where a refrigeration or air conditioning system is installed,
- The company who installed the system must notify the fire department in the jurisdiction where installed
- it shall not be operated below prescribed pressuers
- A field inspection shall be made before it is put into service
- the form or certificate shall be authorized by the Department of Public Safety
5: Pressure vessels with an internal volume of 10 cubic feet or more
- shall use rupture discs or duel pressure relief valves
- shall use pressure relief devices
- shall use fusible plugs
- shall use pressure relief devices or fusible plugs
6: What do you need to do when you install a new system?
- Document the superheat and subcooling reading
- Add refrigerant
- Insulate the suction line before you take a superheat reading
- Have it inspected
7: Pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 22
- 33
- 18
- 50
8: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
9: How many CFMs are required per square foot of commercial office occupied space
- 20 CFM
- 15 CFM
- 5 CFM
- .5 CFM
10: Pressure relief valves shall be marked with the data from
- Section XIII Division of the ASME Boiler & Pressure Code
- Section I Division VIII of ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
11: Most CFC's are
- flammable
- inert but toxic
- toxic
- inert
12: What refrigerant has zero ozone depletion
- HFC
- CFC
- HCFC
- None of the above
13: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.
- 36
- 24
- 48
- 18
14: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
15: What pipe can not be used for refrigeration?
- L
- K
- N
- M
16: When is the only time you can leave a service container attached to a system?
- Leaking system
- Recovery
- Charging
- Both b and c
17: Ammonia shall be discharged into ____________ or a tank containing one gallon of water for every pound of ammonia.
- the atmosphere
- a de-pressurized recovery tank with a silver top and yellow bottom
- a tank containing two pounds of a water/lithium bromide mix for every pound of ammonia
- All of the above
18: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
19: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 1,000
- 10,000
- 100,000
- 100
20: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- regularly
- quarterly
- annually
- bi-annually
21: What is a Category "D" fluid?
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
22: What refrigerant doesn't have to be classifted?
- R-134a
- R-711
- R-717
- R-718
23: Who is permitted to access a refrigeration machine room?
- Anyone, it's a completely safe area
- Authorized persons only
- Any employee
- Contractors only
24: The Board of Boilers adopts by reference
- Montreal Protocol Safety Code
- the 1997 ANSI/ASHRAE Safety Code
- the MACS Pressure Vessel Code of Massachusetts
- MSCA Code
25: R-717 is
- carbon dioxide
- ammonia
- trichloromethane
- water