Topics: ASHRAE/CMR
1: Pipe identification labels are required when the system contains more than
- 120 lbs
- 55 lbs
- 110 lbs
- 65 lbs
2: Single compound Refrigerants are classified by what two criteria?
- Flammability and temperature range
- Flammability and toxicity
- Temperature range and hazardousness
- Weight and color
3: What refrigerant is an inorganic compound?
- R-410A
- Ammonia
- R-132A
- R-22
4: Class T machine room
- shall include closets used for setting equipment
- shall have remote controls to stop the action of the refrigerant compressor
- shall have refrigerant leak detecting systems installed inside and outside the room
- has no flame producing apparatus permanently installed
5: Pressure vessels with an internal volume of 3 cubic feet or less
- shall use fusible plugs
- shall use pressure relief devices
- do not need pressure relief protection
- shall use pressure relief devices or fusible plugs
6: Class A refrigerants are considered
- flammable
- non-flammable
- toxic
- non-toxic
7: When a pressure gauge is permanently installed on a system, it must be ___ times the design pressure of the system.
- 2.2
- 1.2
- 1
- 1.5
8: Pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 33
- 22
- 50
- 18
9: What is a Category "D" fluid?
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
10: What is not a requirement of a class T machine room?
- tight fitting doors
- self-closing doors
- fire hose connection to the building fire protection system
- automatic ventilation
11: Setting a pressure relief device shall not exceed ___ of the design pressure
- 100%
- 90%
- 80%
- 75%
12: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?
- When there is a space 6' or more above it
- When it's used as part of a supply or return air system
- When its white
- When there are sprinklers above
13: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
14: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
15: How far from the window does a relief valve need to be according to ASHRAE-15?
- At least 40'
- At least 20'
- There is no minimum for relief valve and windows.
- At least 30'
16: There can be no airflow from an occupied space through a machine room unless what?
- System is high velocity
- System is ducted and sealed
- Duct is not located in the ceiling
- None of the above.
17: What kind of material can't be used on the outlet of a relief valve?
- Copper
- Aluminum
- PVC
- Stainless Steel
18: No open flames are allowed in the machinery room unless?
- Only when combustion air is provided from outside of the machinery room
- Approved by the installing contractor
- Approved by the authorized person
- Never can be allowed
19: Pressure vessels shall be provided with ___________in accordance with Section VIII of the ASME Boiler & Pressure Vessel Code
- over pressure protection and a rupture disc
- over pressure protection as well as a temperature protection device
- over pressure protection
- Pressure vessels need no type of protection as long as it is hydrostatically tested every three months
20: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 100
- 350
- 50
- 550
21: Liquid level gauges shall have _____________ with one exception being that of the liquid level gauge bull’s eye type.
- color-coded glass to determine type of refrigerant
- moisture indicators
- automatic closing shut-off valves
- All of the above
22: How many CFMs are required per square foot of commercial office occupied space
- 15 CFM
- .5 CFM
- 20 CFM
- 5 CFM
23: Institutional occupancy is
- a premise or that portion of a premise where large numbers of people congregate and from which occupants cannot quickly vacate the space.
- a premise or that portion of a premise from which, because they are disabled, debilitated, or confined, occupants cannot readily leave without the assistance of others.
- a premise or that portion of a premise where people transact business, receive personal service, or purchase food and other goods.
- None of the above
24: How much clearance do you need around the perimeter of electrical panels?
- 36"
- 12"
- 24"
- 18"
25: A 3-cubic foot receiver must have what type of relief valve?
- fusible plug
- relief valve
- rupture device
- none of the above