Topics: ASHRAE/CMR
1: Stop valves shall not be permitted between the system and the
- service valve
- condenser
- bleed valve
- relief valve
2: Joints in piping for refrigeration containing parts must withstand temperatures of ___?
- 700F
- 1000F
- 600F
- 800F
3: What is the refrigerant chlorodifluoromethane?
- R-22
- R-12
- R-134a
- R-123
4: High pressure controls should be set no higher than
- 10% of set point
- 90% of set point
- 80% of set point
- 25% of set point
5: A class B1 refrigerant is considered
- toxic and somewhat flammable
- non-toxic and non-flammable
- toxic but non-flammable
- non-toxic but highly flammable
6: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
7: R-22 falls under which safety classification?
- B-1
- A-2
- B-2
- A-1
8: NH3 is
- R-508A
- ammonia
- lithium bromide
- R-718
9: R-410A is classified as a ____ refrigerant on the safety matrix.
- B-2
- A-1
- B-1
- A-2
10: Class 3 refrigerants are
- toxic
- non-flammable
- highly flammable
- non-toxic
11: What is not a requirement of a class T machine room?
- fire hose connection to the building fire protection system
- tight fitting doors
- automatic ventilation
- self-closing doors
12: Single compound Refrigerants are classified by what two criteria?
- Flammability and temperature range
- Flammability and toxicity
- Weight and color
- Temperature range and hazardousness
13: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 660 lbs
- 55 lbs
- 330 lbs.
- 550 lbs
14: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- phosgene gas sening
- CO Sensing
- A group sensing
- refrigerant sensing
15: Ammonia can come in contact with _______ ?
- Aluminum
- Brass
- Copper
- Copper tubing
16: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class A machinery room
- Class B machinery room
- Class T machinery room
- Class M machinery room
17: Refrigerant restricted in 2004 but used for transition for decades:
- R-123
- R-134A
- R-22
- R-11
18: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.
- ammonia
- CFC-11
- Lithium bromide
- HCFC-123
19: Direct systems using Group II refrigerants
- shall be installed per instruction of the AHJ
- shall not be used for air condition for human comfort
- shall be allowed to be used for human comfort.
- shall be installed in Class T machinery rooms
20: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 100
- 350
- 550
21: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
22: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Place sign, check for leaks, and insulate suction line
- you can never change refrigerants
- Make sure its compatible, notify owner, and notify AHJ.
- Nothing must be done
23: What type of relief valve is used on a CO2 system?
- fusible plug
- rupture disc
- glove disc
- gate valve
24: What type of copper is not permitted on refrigeration systems?
- Type M
- Type K
- Type N
- Type L
25: Pressure vessels with an internal volume of 3 cubic feet or less
- shall use pressure relief devices
- shall use fusible plugs
- shall use pressure relief devices or fusible plugs
- do not need pressure relief protection