Topics: ASHRAE/CMR
1: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 550
- 100
- 350
2: Joints in refrigeration piping must be _____ before being covered?
- Leak tested
- Inspected
- Pressurized
- Insulated
3: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
4: A declaration test is needed when the system contains more than
- 110 lbs
- 120 lbs
- 55 lbs
- 65 lbs
5: Direct systems using Group II refrigerants
- shall be allowed to be used for human comfort.
- shall be installed per instruction of the AHJ
- shall not be used for air condition for human comfort
- shall be installed in Class T machinery rooms
6: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- the vapor side of the system
- high side of the system
- the liquid side of the system
7: Pipe identification labels are required when the system contains more than
- 65 lbs
- 120 lbs
- 110 lbs
- 55 lbs
8: What type of material can't be used on the outlet of a relief valve?
- Magnesium alloy
- PVC
- Copper
- Stainless steel
9: Each machinery room shall contain
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- high and low pressure controls
10: The gauge thickness required on a CO2 tank construction is
- 5/16"
- 1/8"
- 1/16"
- 3/32"
11: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 100,000
- 100
- 10,000
- 1,000
12: What section governs pressure vessels?
- OSHA
- Section 1 ASHREA 15 ASME fired
- Section ASHREA 34
- Section 8 ASHREA 15 ASME unfired
13: An example of direct system is
- rooftop unit
- chiller
- absorber
- none of the above
14: Pressure vessels with an internal volume of 3 cubic feet or less
- do not need pressure relief protection
- shall use pressure relief devices or fusible plugs
- shall use fusible plugs
- shall use pressure relief devices
15: How many gallons of water per pound of ammonia do you need?
- 20
- 15
- 1
- 5
16: When an inspection is needed, how often must it be done?
- every 18 months
- annually
- every 24 months
- every 36 months
17: Which refrigerant class listed below is the most flammable?
- A2
- B2
- A3
- C3
18: What must be done to refrigerant pipes before being buried?
- Coated
- Encased
- Certified
- Leaked checked
19: R-11 belongs to Group
- A-1
- B-3
- B-1
- A-2
20: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
- evaporator
- compressor
- outside the machinery room
- boiler
21: Who approves containers for refrigerants?
- D.O.E
- D.O.D
- D.O.T
- E.P.A
22: Name an HCFC refrigerant(s):
- R-22
- R-123
- R-11
- both a & b
23: Pressure relief valves shall be marked with the data from
- Section XIII Division of the ASME Boiler & Pressure Code
- Section VIII Division of the ASME Boiler & Pressure Code
- Section I Division VIII of ASME Boiler & Pressure Code
- Section IV Division of the ASME Boiler & Pressure Code
24: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by
- District Engineering Inspectors
- Commissioned Inspectors
- Master licensed Technician
- both a or b
25: Where must a refrigeration contractor's license number be displayed?
- Trucks, license plates, and uniforms
- Truck, office, every job, and on all equipment
- Uniforms, checks, and invoices.
- Trucks, invoices, and advertising