Topics: ASHRAE/CMR
1: A pressure relief should be located at least _______ from windows and doors.
- 20'
- 15'
- 30'
- 25'
2: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- phosgene gas sening
- CO Sensing
- refrigerant sensing
- A group sensing
3: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 2.5, 2.5
- 2.5, 3.0
- 6.6, 6.6
- 3.0, 3.5
4: NH3 is
- lithium bromide
- ammonia
- R-718
- R-508A
5: Who authorizes changes to the safety codes?
- Person who pulled the permit
- Contractor who last serviced the system.
- Board of Boilers
- Person in charge of the facility
6: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- Machinery rooms need not be vented
- the outdoors
- the return air ducted system
- the mechanical room housing the refrigeration system
7: How many gallons of water per pound of ammonia do you need?
- 1
- 5
- 20
- 15
8: What would be the classification for Stop & Shop grocery store?
- Place of assembly
- Instituional
- Large mercantile
- Industrial
9: R-22 falls under which safety classification?
- A-1
- A-2
- B-1
- B-2
10: What type of refrigerants are NOT flammable?
- CHC
- HFC
- HCFC
- All of the above
11: Refrigerants shall be classified by
- color codes
- maximum permissible quantities of each group
- requirements for commercial, industrial, and residential occupancies
- toxicity and flammability
12: What section of ASHRAE-15 governs pressure vessels?
- Section 6 ASHRAE-34 ASME VIII unfired
- Section 9 ASHRAE-15 ASME VIII unfired
- OSHA
- Section 7 ASHRAE-15 ASME VIII fired
13: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- bi-annually
- regularly
- quarterly
- annually
14: Each machinery room shall contain
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- high and low pressure controls
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
15: When is the only time you can leave a service container attached to a system?
- Leaking system
- Recovery
- Charging
- Both b and c
16: When should a relief valve start to function?
- At it's set pressure
- Two times it's working pressure
- 10 psi before it's set pressure
- Before the purge station discharges
17: What would be the classification of a prison?
- Place of assembly
- Industrial
- Institutional
- Large mercantile
18: A movie theater would be considered a
- commercial occupancy
- institutional occupancy
- public assembly occupancy
- mixed occupancy
19: What type of copper is not permitted on refrigeration systems?
- Type M
- Type L
- Type N
- Type K
20: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
21: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
22: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
23: How many groups of refrigerants are there?
- 5
- 7
- 3
- 1
24: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
25: A High-Probablity system
- is such that a leak of refrigerant from failed connections will enter the occupied space
- is a system highly likely to leak from a failed connection or component of such system
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is such that a leak of refrigerant from failed connections will enter the unoccupied space