Topics: ASHRAE/CMR
1: Pressure vessels having an inside diameter of 6” or less shall be protected by
- either a fusible plug or a pressure relief device
- a fusible plug
- a pressure relief device
- Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
2: Where are the three places that the discharge from an ammonia relief valve be piped?
- To chemical neutralizing tank only
- Underground, into drain, into mechanical room
- Atmosphere, Tank containing water, where the AHJ indicates.
- None of the above.
3: Class 3 refrigerants are
- non-flammable
- highly flammable
- non-toxic
- toxic
4: No open flames are allowed in the machinery room unless?
- Approved by the authorized person
- Only when combustion air is provided from outside of the machinery room
- Approved by the installing contractor
- Never can be allowed
5: R-22 falls under which safety classification?
- A-1
- B-2
- B-1
- A-2
6: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.
- 15
- 20
- 50
- 75
7: Liquid level gauges shall have _____________ with one exception being that of the liquid level gauge bull’s eye type.
- color-coded glass to determine type of refrigerant
- moisture indicators
- automatic closing shut-off valves
- All of the above
8: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
9: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
10: What would be the classification for Stop & Shop grocery store?
- Large mercantile
- Place of assembly
- Industrial
- Instituional
11: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 6.6
- 110
- 1,000
- 330
12: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of
- the ASME Boiler and Pressure Vessel Code
- Section 11.3.1.5 ASHRAE 15 Standard
- the ANSI Standard 10.7.2
- both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5
13: R-717 is
- ammonia
- trichloromethane
- carbon dioxide
- water
14: What was the main reason for enacting the no venting rule of July 1, 1992?
- Ozone depletion
- Green house effect
- Global warming potential
- All of the above
15: The certificate of inspection
- shall be posted and protected from dirt, water, and other elements
- shall be posted on the compressor shell or electrical panel at the unit
- shall be authorized by a notarized insurance company
- shall be $20 and an additional fee of $1 for each tone above 20 tons
16: Pressure vessels having design pressures of 15 psig or less shall have the strength to withstand at least ______times the design pressure.
- 2.5
- 3.0
- 5.5
- 2.0
17: Class T machine room
- has no flame producing apparatus permanently installed
- shall have remote controls to stop the action of the refrigerant compressor
- shall have refrigerant leak detecting systems installed inside and outside the room
- shall include closets used for setting equipment
18: Defined process piping by code CMR (528)
- Any piping that conveys a solid, liquid or gas that is not part of the plumbing or fire protection system
- Any piping in an industrial space
- Any piping in an industrial or commercial space
- All of the above
19: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
20: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a
- mercantile occupancy
- business occupancy
- public assembly occupancy.
- commercial occupancy
21: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.
- there is no Group B1 refrigerants
- the same
- lower
- higher
22: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested
- regularly
- bi-annually
- quarterly
- annually
23: What is an example of institutional occupancy?
- Hospital
- Shopping mall
- Dorms
- Football stadium
24: A class A3 refrigerant is considered
- non-toxic and non-flammable
- non-toxic but highly flammable
- toxic and non-flammable
- toxic and somewhat flammable
25: What must be done to all doors and access points in duct work going through a mechanical room?
- Must be hindged
- Must be screwed shut
- Must be sealed and gasketed
- All of the above