ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: How many CFMs are required per square foot of commercial office occupied space

  • 5 CFM
  • 15 CFM
  • .5 CFM
  • 20 CFM

2: Which of the following are considered inorganic refrigerants?

  • R-717 and R-718
  • 410A and R-407C
  • R-500 and R-502
  • None of the above

3: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.

  • 75
  • 20
  • 15
  • 50

4: Whoever owns/uses a refrigeration or air conditioning system covered by this code

  • must notify the Department of Public Safety prior to starting the system
  • shall be licensed by the Commonwealth of Massachusetts according to CMR 522
  • shall make application for inspections to the Chief of Inspectors
  • None of the above

5: How many different groups of refrigerants are there?

  • 11
  • 7
  • 15
  • 3

6: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.

  • ammonia
  • HCFC-123
  • Lithium bromide
  • CFC-11

7: Pressure vessels with an internal volume of 3 cubic feet or less

  • do not need pressure relief protection
  • shall use fusible plugs
  • shall use pressure relief devices
  • shall use pressure relief devices or fusible plugs

8: Trichlorofluoromethane is the name of what refrigerant?

  • R-113
  • R-11
  • R-12
  • R-502

9: When a refrigeration or air conditioning system is installed

  • the form of certificate shall be authorized by the Department of Pubic safety
  • it shall not be operated below prescribed pressures
  • a field inspection shall be made before it is put into service
  • it shall be approved by the owner for proper operation.

10: What type of pressure relief device is used on a CO2 system?

  • Rupture disk
  • Glove valve
  • Fusible plug
  • Gate valve

11: What would be the classification of a prison?

  • Institutional
  • Industrial
  • Place of assembly
  • Large mercantile

12: What is not a requirement of a Class T machine room?

  • Self-closing doors
  • Automatic ventilation
  • Tight fitting doors
  • Fire hose connected to the building fire protection system.

13: Stop valves shall not be permitted between the system and the

  • relief valve
  • service valve
  • condenser
  • bleed valve

14: Joints in piping for refrigeration containing parts must withstand temperatures of ___?

  • 800F
  • 600F
  • 700F
  • 1000F

15: The gauge thickness required on a CO2 tank construction is

  • 1/16"
  • 5/16"
  • 1/8"
  • 3/32"

16: Liquid level gauges must be provided with what?

  • A relief valve
  • Automatic shut-offs
  • A low level mark
  • A red line

17: A hotel is considered a _______ occupancy.

  • commercial
  • residential
  • mercantile
  • institutional

18: A declaration test is needed when the system contains more than

  • 55 lbs
  • 110 lbs
  • 65 lbs
  • 120 lbs

19: pressure relief valves must discharge to the atmosphere at a location not less than 15 feet from ground level and ____ feet from any window, ventilation opening, or exits of buildings.

  • 25
  • 15
  • 10
  • 20

20: What is R-611’s ASHRAE Safety Code?

  • A2
  • B2
  • B3
  • C3

21: What is a Category "M" fluid?

  • A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
  • A typical refrigerant used on newer air conditioning and heat pump systems
  • Any fluid that exceeds 150 psig and has design temperatures over 366F
  • A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F

22: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by

  • District Engineering Inspectors
  • Commissioned Inspectors
  • Master licensed Technician
  • both a or b

23: When air is ducted through a machine room that services occupied space, What must be done?

  • Flanged and gasketed
  • Insulated and cross broke
  • Ducted and sealed
  • Welded and seamed.

24: According to ASHRAE Standard-15 9.8 Positive Displacement Compressor Protection, the pressure-relief device discharge into

  • the low-pressure side of the system
  • the high side of the system
  • the liquid receiver
  • both a and c are correct

25: Refrigerants shall be classified by

  • toxicity and flammability
  • requirements for commercial, industrial, and residential occupancies
  • color codes
  • maximum permissible quantities of each group