Topics: ASHRAE/CMR
1: When a pressure gauge is permanently installed on a system, it must be ___ times the design pressure of the system.
- 1
- 2.2
- 1.2
- 1.5
2: Which refrigerant(s) is an HFC?
- R-22
- R-410A
- R-502
- All of the above
3: The Department that certifies the transportation of refrigerant is the
- EPO
- RSES
- EPA
- DOT
4: What type refrigerant is NOT ozone depleting?
- Halon
- CFC
- HFC
- HCFC
5: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- the return air ducted system
- Machinery rooms need not be vented
- the outdoors
- the mechanical room housing the refrigeration system
6: A plug containing an alloy that will melt at a specific temperature to relief pressure is a
- fusible plug
- relief plug
- fusion plug
- rupture plug
7: What is the refrigerant dichlorodifluoromethane?
- R-22
- R-134A
- R-123
- R-12
8: A class B2 refrigerant is considered
- non-toxic and non-flammable
- toxic and somewhat flammable
- toxic and non-flammable
- non-toxic and highly flammable
9: Ammonia belongs to Group
- B-2
- A-1
- B-1
- A-2
10: Trichlorofluoromethane is the name of what refrigerant?
- R-502
- R-113
- R-12
- R-11
11: _____ and its alloys are suitable for use with ammonia systems.
- Zinc
- Magnesium
- Aluminum
- Copper
12: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- shall have a pressure limiting device installed on the high side of the system
- shall be inspected by the Boiler of Inspectors bi-annually
- does not require a pressure-limiting device
- shall have a pressure limiting device and a pressure relief valve installed
13: Walls and doors of a machinery room shall be at least _____ hour(s) fire rated.
- 1
- 2
- 3
- 5
14: Each machinery room shall contain
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- high and low pressure controls
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
15: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.
- 80%
- 90%
- 75%
- 100%
16: Pipe identification labels are required when the system contains more than
- 110 lbs
- 65 lbs
- 55 lbs
- 120 lbs
17: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
18: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 2.5, 2.5
- 6.6, 6.6
- 3.0, 3.5
- 2.5, 3.0
19: Systems containing more than 110 pounds must have stop valves located at the
- compressor suction inlet
- compressor discharge outlet
- receiver inlet and outlet
- All of the above
20: High pressure controls should be set no higher than
- 10% of set point
- 25% of set point
- 90% of set point
- 80% of set point
21: According to ASHRAE Standard-15 9.8 Positive Displacement Compressor Protection, the pressure-relief device discharge into
- the low-pressure side of the system
- the high side of the system
- the liquid receiver
- both a and c are correct
22: What is a Category "D" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
23: A relief valve shall be located at least ___ above grade.
- 15'
- 36'
- 25'
- 10'
24: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.
- 36
- 24
- 18
- 48
25: The Board of Boilers adopts by reference
- the MACS Pressure Vessel Code of Massachusetts
- MSCA Code
- Montreal Protocol Safety Code
- the 1997 ANSI/ASHRAE Safety Code