Topics: ASHRAE/CMR
1: Single compound Refrigerants are classified by what two criteria?
- Flammability and toxicity
- Temperature range and hazardousness
- Weight and color
- Flammability and temperature range
2: Which refrigerant replaced R-12?
- R-410A
- R-22
- R-407A
- R-134A
3: What is the minimum height refrigeration piping should be placed against walls?
- 7.25'
- 72"
- 6'
- Ceiling height
4: No open flames are allowed in the machinery room unless?
- Only when combustion air is provided from outside of the machinery room
- Approved by the installing contractor
- Never can be allowed
- Approved by the authorized person
5: What must be done to refrigerant pipes before being buried?
- Coated
- Leaked checked
- Encased
- Certified
6: A High-Probability System
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
7: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
8: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
9: When testing systems using non-positive displacement compressors, the entire system shall be considered for test purposes as the low side.
- True
- False
10: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
11: Where a refrigeration or air conditioning system is installed,
- A field inspection shall be made before it is put into service
- it shall not be operated below prescribed pressuers
- The company who installed the system must notify the fire department in the jurisdiction where installed
- the form or certificate shall be authorized by the Department of Public Safety
12: What does safe access mean?
- Locked doors
- A clear unobstructed path to the equipment and controls
- Well-lit exit signs
- OSHA approved
13: The Board of Boilers adopts by reference
- Montreal Protocol Safety Code
- MSCA Code
- the MACS Pressure Vessel Code of Massachusetts
- the 1997 ANSI/ASHRAE Safety Code
14: Which refrigerant class listed below is the most flammable?
- A-3
- B-2
- C-3
- A-1
15: Most CFC's are
- flammable
- toxic
- inert but toxic
- inert
16: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a
- commercial occupancy
- public assembly occupancy.
- mercantile occupancy
- business occupancy
17: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.
- 6.6, 6.6
- 2.5, 2.5
- 3.0, 3.5
- 2.5, 3.0
18: What must be done if refrigeration lines pass through a concrete floor?
- insulated
- installed through a pipe casing
- moisture barrier
- leak checked
19: The color code of a tank of ammonia is
- lavender
- white
- light green
- silver
20: How far from the ground does a relief valve need to be?
- Not more than 3' above grade
- At least 25' above grade
- At least 15' above grade
- At least 20' above grade
21: Who authorizes changes to the safety codes?
- Board of Boilers
- Contractor who last serviced the system.
- Person who pulled the permit
- Person in charge of the facility
22: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.
- 100
- 110
- 80
- 90
23: What must be done to refrigerant pipes before being buried ?(8.10.4)
- Classifed
- Insulated and installed in a pipe duct (Encased)
- Leak checked
- Certified
24: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants
- lower
- higher
- there is no Group B1 refrigerants
- the same
25: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- licensed welder
- competent welder
- welder qualified
- licensed technician