Topics: ASHRAE/CMR
1: All electrical work done on refrigeration systems must comply with
- ASHREA-15 Section 9.2.1
- OSHA
- NEC and Massachusetts Modifications
- Department of Energy
2: What do you need to do when you install a new system?
- Document the superheat and subcooling reading
- Insulate the suction line before you take a superheat reading
- Add refrigerant
- Have it inspected
3: A High-Probability System
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter an unoccupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
4: Pressure vessels having design pressures of 15 psig or less shall have the strength to withstand at least ______times the design pressure.
- 2.0
- 2.5
- 5.5
- 3.0
5: Pressure vessels having an inside diameter of 6” or less shall be protected by
- a fusible plug
- a pressure relief device
- either a fusible plug or a pressure relief device
- Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
6: What must be done to refrigerant pipes before being buried ?(8.10.4)
- Classifed
- Leak checked
- Certified
- Insulated and installed in a pipe duct (Encased)
7: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.
- True
- False
8: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 1,000
- 110
- 330
- 6.6
9: A premise or that portion of a premise where people transact business, receive personal service, or purchase foods, other goods is considered a
- mercantile occupancy
- commercial occupancy
- business occupancy
- public assembly occupancy.
10: A High-Probablity system
- is such that a leak of refrigerant from failed connections will enter the occupied space
- is a system highly likely to leak from a failed connection or component of such system
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is such that a leak of refrigerant from failed connections will enter the unoccupied space
11: Group A3 refrigerants have a ______ flammability rating than Group B1 refrigerants
- higher
- there is no Group B1 refrigerants
- lower
- the same
12: What is an example of institutional occupancy?
- Football stadium
- Dorms
- Hospital
- Shopping mall
13: R-123 belongs to Group
- B-3
- B-1
- B-2
- A-3
14: What would be the classification for Stop & Shop grocery store?
- Place of assembly
- Instituional
- Large mercantile
- Industrial
15: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 25
- 66
- 50
- 22
16: No open flames are allowed in the machinery room unless?
- Only when combustion air is provided from outside of the machinery room
- Approved by the authorized person
- Never can be allowed
- Approved by the installing contractor
17: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
18: What is not a requirement of a Class T machine room?
- Self-closing doors
- Fire hose connected to the building fire protection system.
- Tight fitting doors
- Automatic ventilation
19: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- high side of the system
- the vapor side of the system
- the liquid side of the system
20: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with R-11
- Flush with ammonia
- Flush with R-718
- Flush with RX-11
21: Doors communicating with outside from a mechanical room must be?
- Self-closing, wooden, fire door
- Self-closing, aligned, fire door
- Steel, approved, weather-stripped
- Self-closing, approved, fire door
22: What is the refrigerant dichlorodifluoromethane?
- R-12
- R-134A
- R-123
- R-22
23: A Low-Probability System
- is such that a leak of refrigerant from a failed connection can not enter the occupied space
- is such that a leak of refrigerant from a failed connection will enter the occupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak form a failed connection or component of such system
24: What refrigerant doesn't have to be classified?
- R-134A
- R-422A
- R-718
- R-717
25: The certificate of inspection
- shall be posted and protected from dirt, water, and other elements
- shall be authorized by a notarized insurance company
- shall be posted on the compressor shell or electrical panel at the unit
- shall be $20 and an additional fee of $1 for each tone above 20 tons