Topics: ASHRAE/CMR
1: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
2: A plug containing an alloy that will melt at a specific temperature to relief pressure is a
- relief plug
- fusion plug
- rupture plug
- fusible plug
3: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 1,000
- 6.6
- 110
- 330
4: Stop valves shall not be permitted between the system and the
- relief valve
- service valve
- bleed valve
- condenser
5: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the
- 24 volt secondary side of the Class 2 transformer to the thermostat
- first disconnect in
- breaker panel in
- load-side of the contactor in
6: Pressure vessels of 10 cubic feet or more gross volume shall use
- at least one rupture member
- a dual pressure-relief valve if charging into the atmosphere
- at least three means of discharge and/or rupture discs
- both a and b are correct
7: Which of the following is an inorganic refrigerant?
- R-22
- Ammonia
- Chlorofluorocarbons
- All of the above
8: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by
- District Engineering Inspectors
- Commissioned Inspectors
- Master licensed Technician
- both a or b
9: Pressure vessels having an inside diameter of 6” or less shall be protected by
- a pressure relief device
- a fusible plug
- Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
- either a fusible plug or a pressure relief device
10: The Department that certifies the transportation of refrigerant is the
- RSES
- DOT
- EPA
- EPO
11: A 3-cubic foot receiver must have what type of relief valve?
- fusible plug
- relief valve
- rupture device
- none of the above
12: Refrigerant piping crossing an open space that affords passageway in any building shall not be less than _____ feet above the floor unless piping is located against the ceiling.
- 9.00'
- 7.25'
- 7.00'
- 8'4"
13: Ammonia belongs to Group
- A-1
- B-2
- B-1
- A-2
14: Can you use Ammonia in industrial applications?
- No, never
- When mixed with R-718
- Yes, always
- Yes, Under certain condidtions
15: What must be done to refrigerant pipes before being buried ?(8.10.4)
- Classifed
- Leak checked
- Insulated and installed in a pipe duct (Encased)
- Certified
16: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
17: Pressure vessel having an inside diameter exceeding 6” with an internal pressure greater than 15psig shall be marked directly on or on the nameplate the letters _______________ signifying compliance with the ASME Boiler & Pressure Vessel Code.
- “UV”
- “U” or “UM”
- “UL”
- “UM” and “UV”
18: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Nothing must be done
- Place sign, check for leaks, and insulate suction line
- Make sure its compatible, notify owner, and notify AHJ.
- you can never change refrigerants
19: What is a Category "M" fluid?
- A typical refrigerant used on newer air conditioning and heat pump systems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
- Any fluid that exceeds 150 psig and has design temperatures over 366F
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
20: Joints in refrigeration piping must be _____ before being covered?
- Insulated
- Leak tested
- Inspected
- Pressurized
21: What should not (and can not) be located between a pressure imposing device and a pressure-limiting device?
- Foot valve
- Muffler
- Stop valve
- Moisture indicator
22: Who authorizes changes to the safety codes?
- Contractor who last serviced the system.
- Person in charge of the facility
- Board of Boilers
- Person who pulled the permit
23: What is Trichlorotrifluoromethane?
- R-11
- R-13
- R-12
- R-113
24: Pressure vessels nameplate markings must be compliant with the
- ASHRAE 34 Standards
- CMR-588 & CMR-528
- ASME Boiler and Pressure Vessel Code
- All of the Above
25: There can be no airflow from an occupied space through a machine room unless what?
- System is high velocity
- System is ducted and sealed
- Duct is not located in the ceiling
- None of the above.