Topics: ASHRAE/CMR
1: Liquid level gauges must be provided with what?
- A low level mark
- Automatic shut-offs
- A relief valve
- A red line
2: What do you need to do when you install a new system?
- Document the superheat and subcooling reading
- Add refrigerant
- Insulate the suction line before you take a superheat reading
- Have it inspected
3: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
4: What type of relief valve is used on low pressure centrifugal compressor systems?
- Spring-loaded relief valve
- Rupture disc
- Purge relief
- None of the above
5: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- licensed technician
- licensed welder
- welder qualified
- competent welder
6: Stop valves shall not be permitted between the system and the
- service valve
- condenser
- bleed valve
- relief valve
7: What is a Category "D" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
8: The certificate of inspection
- shall be posted on the compressor shell or electrical panel at the unit
- shall be authorized by a notarized insurance company
- shall be posted and protected from dirt, water, and other elements
- shall be $20 and an additional fee of $1 for each tone above 20 tons
9: How many flammability classifications are refrigerants in?
- 7
- 3
- 5
- 2
10: Defined process piping by code CMR (528)
- Any piping that conveys a solid, liquid or gas that is not part of the plumbing or fire protection system
- Any piping in an industrial space
- Any piping in an industrial or commercial space
- All of the above
11: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
12: Which refrigerant class listed below is the most flammable?
- A3
- B2
- C3
- A2
13: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 22
- 25
- 50
- 66
14: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with R-11
- Flush with RX-11
- Flush with R-718
- Flush with ammonia
15: No open flames are allowed in the machinery room unless?
- Approved by the installing contractor
- Never can be allowed
- Approved by the authorized person
- Only when combustion air is provided from outside of the machinery room
16: Ammonia belongs to Group
- B-1
- B-2
- A-2
- A-1
17: When should a relief valve start to function?
- 10 psi before it's set pressure
- Two times it's working pressure
- Before the purge station discharges
- At it's set pressure
18: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 100
- 350
- 550
19: What type refrigerant is NOT ozone depleting?
- HCFC
- CFC
- HFC
- Halon
20: Ammonia shall be discharged into ____________ or a tank containing one gallon of water for every pound of ammonia.
- the atmosphere
- a de-pressurized recovery tank with a silver top and yellow bottom
- a tank containing two pounds of a water/lithium bromide mix for every pound of ammonia
- All of the above
21: Who authorizes changes to the safety codes?
- Person who pulled the permit
- Board of Boilers
- Contractor who last serviced the system.
- Person in charge of the facility
22: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
23: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.
- True
- False
24: A pressure relief should be located at least _______ from windows and doors.
- 25'
- 15'
- 20'
- 30'
25: What is not a requirement of a Class T machine room?
- Self-closing doors
- Automatic ventilation
- Fire hose connected to the building fire protection system.
- Tight fitting doors