ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: When is the only time you can leave a service container attached to a system?

  • Leaking system
  • Recovery
  • Charging
  • Both b and c

2: Methyl Chloride is a halogenated refrigerant and should not come in contact with

  • aluminum
  • zinc
  • magnesium
  • all of the above

3: Pressure vessels shall be provided with ___________in accordance with Section VIII of the ASME Boiler & Pressure Vessel Code

  • over pressure protection
  • Pressure vessels need no type of protection as long as it is hydrostatically tested every three months
  • over pressure protection as well as a temperature protection device
  • over pressure protection and a rupture disc

4: Can ammonia be used on domestic system?

  • no, unless there is proper ventilation system installed
  • yes
  • no
  • yes, for systems under 10 tons

5: How many CFMs are required per square foot of commercial office occupied space

  • 20 CFM
  • 15 CFM
  • .5 CFM
  • 5 CFM

6: _____ and its alloys are suitable for use with ammonia systems.

  • Aluminum
  • Magnesium
  • Copper
  • Zinc

7: Before you change the type of refrigerant in a refrigeration system, what three things must be done?

  • place sign, check for leaks, insulate
  • make sure it's compatible, notify owner, notify A.H.J
  • you can't change refrigerants
  • nothing must be done

8: Ammonia is under what safety classification?

  • B3
  • B1
  • B2
  • A3

9: How many gallons of water do you need per pound of ammonia?

  • 1
  • 100
  • 50
  • 10

10: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?

  • Flush with RX-11
  • Flush with R-11
  • Flush with R-718
  • Flush with ammonia

11: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the

  • load-side of the contactor in
  • 24 volt secondary side of the Class 2 transformer to the thermostat
  • first disconnect in
  • breaker panel in

12: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.

  • 75
  • 15
  • 50
  • 55

13: A pressure vessel having an inside diameter of 6” or less shall be sufficient to withstand ____times the pressure of the saturation temperature of the refrigerant or ____times the critical pressure of the refrigerant, whichever is less.

  • 6.6, 6.6
  • 2.5, 2.5
  • 2.5, 3.0
  • 3.0, 3.5

14: When must refrigeration system covered by the code be inspected?

  • Annually
  • Annually and when installed
  • Upon installation
  • Not required

15: What must be done to refrigerant pipes before being buried ?(8.10.4)

  • Insulated and installed in a pipe duct (Encased)
  • Certified
  • Leak checked
  • Classifed

16: All electrical work done on refrigeration systems must comply with

  • NEC and Massachusetts Modifications
  • ASHREA-15 Section 9.2.1
  • Department of Energy
  • OSHA

17: B3 refrigerants are considered

  • toxic but non-flammable
  • toxic and highly flammable
  • non-toxic but flammable
  • non-toxic but non-flammable

18: What type of material can't be used on the outlet of a relief valve?

  • Magnesium alloy
  • PVC
  • Stainless steel
  • Copper

19: What is the refrigerant dichlorodifluoromethane?

  • R-123
  • R-12
  • R-134A
  • R-22

20: What refrigerant doesn't have to be classifted?

  • R-717
  • R-134a
  • R-711
  • R-718

21: An example of direct system is

  • rooftop unit
  • chiller
  • absorber
  • none of the above

22: What type of refrigerants are NOT flammable?

  • CHC
  • HFC
  • HCFC
  • All of the above

23: The 522 CMR 9.00 has adopted for reference ASHRAE ____

  • III
  • 25
  • 10
  • 15

24: copper and its alloys shall not be used in contact with _____ except as a component of bronze alloys for bearing or other non-refrigerant containing uses.

  • CFC-11
  • Lithium bromide
  • ammonia
  • HCFC-123

25: Stop valves shall not be permitted between the system and the

  • relief valve
  • service valve
  • condenser
  • bleed valve