Topics: ASHRAE/CMR
1: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
2: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within
- 2 months
- 1 week
- 14 days
- 30 days
3: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class A machinery room
- Class T machinery room
- Class B machinery room
- Class M machinery room
4: Name a CFC refrigerant(s):
- R-11
- R-12
- R-123
- both a & b
5: A pressure relief should be located at least _______ from windows and doors.
- 20'
- 25'
- 15'
- 30'
6: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 10,000
- 100,000
- 100
- 1,000
7: A High-Probablity system
- is such that a leak of refrigerant from failed connections will enter the unoccupied space
- is such that a leak of refrigerant from failed connections will enter the occupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is a system highly likely to leak from a failed connection or component of such system
8: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 50
- 25
- 66
- 22
9: What type of refrigerants are NOT flammable?
- CHC
- HFC
- HCFC
- All of the above
10: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- the vapor side of the system
- high side of the system
- the liquid side of the system
11: The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves shall not exceed
- 550 lbs
- 660 lbs
- 55 lbs
- 330 lbs.
12: Each machinery room shall contain
- high and low pressure controls
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
13: Halogenated refrigerants cannot be used with what material?
- Magnesium alloy
- Copper
- Stainless steel
- Aluminum
14: Which refrigerant replaced R-12?
- R-134A
- R-22
- R-407A
- R-410A
15: Class 3 refrigerants are
- highly flammable
- non-toxic
- non-flammable
- toxic
16: Low temperature systems should have what?
- High pour point
- Low pour point
- High viscosity
- None of the above
17: Can ammonia be used on domestic system?
- no
- yes
- yes, for systems under 10 tons
- no, unless there is proper ventilation system installed
18: A class A3 refrigerant is considered
- toxic and somewhat flammable
- non-toxic and non-flammable
- non-toxic but highly flammable
- toxic and non-flammable
19: What would be the classification of a prison?
- Institutional
- Industrial
- Large mercantile
- Place of assembly
20: What is the refrigerant chlorodifluoromethane?
- R-134a
- R-123
- R-12
- R-22
21: Which occupancy can ammonia be used in?
- depends on the quantity of freon
- redifential
- commercial
- industrial
22: Where a refrigeration or air conditioning system is installed,
- A field inspection shall be made before it is put into service
- The company who installed the system must notify the fire department in the jurisdiction where installed
- it shall not be operated below prescribed pressuers
- the form or certificate shall be authorized by the Department of Public Safety
23: Fusible plugs must have what marked on them?
- Melting temperature in F
- Melting temperature in C
- Opening pressure
- All of the above
24: Which of the following are considered inorganic refrigerants?
- R-717 and R-718
- 410A and R-407C
- R-500 and R-502
- None of the above
25: Class A refrigerants are considered
- flammable
- non-flammable
- toxic
- non-toxic