ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: What refrigerant doesn't have to be classified?

  • R-717
  • R-134A
  • R-718
  • R-422A

2: A High-Probability System

  • is a system highly likely to leak form a failed connection or component of such system
  • is such that any leak will cause injury or death to anyone within a 100 square foot area
  • is such that a leak of refrigerant from a failed connection will enter an unoccupied space
  • is such that a leak of refrigerant from a failed connection will enter the occupied space

3: How many groups of refrigerants are there?

  • 5
  • 7
  • 1
  • 3

4: How many CFMs are required per square foot of commercial office occupied space

  • .5 CFM
  • 5 CFM
  • 15 CFM
  • 20 CFM

5: R-410A is classified as a ____ refrigerant on the safety matrix.

  • A-1
  • B-2
  • A-2
  • B-1

6: Direct systems using Group II refrigerants

  • shall be allowed to be used for human comfort.
  • shall be installed per instruction of the AHJ
  • shall not be used for air condition for human comfort
  • shall be installed in Class T machinery rooms

7: When an inspection is needed, how often must it be done?

  • every 18 months
  • annually
  • every 24 months
  • every 36 months

8: Setting a pressure relief device shall not exceed ___ of the design pressure

  • 90%
  • 100%
  • 75%
  • 80%

9: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.

  • 80%
  • 90%
  • 75%
  • 100%

10: Joints in piping for refrigeration containing parts must withstand temperatures of ___?

  • 1000F
  • 800F
  • 600F
  • 700F

11: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.

  • Machinery rooms need not be vented
  • the return air ducted system
  • the mechanical room housing the refrigeration system
  • the outdoors

12: Refrigerant piping crossing an open space that affords passageway in any building shall not be less than _____ feet above the floor unless piping is located against the ceiling.

  • 7.25'
  • 9.00'
  • 8'4"
  • 7.00'

13: Halogenated refrigerants cannot be used with what material?

  • Stainless steel
  • Magnesium alloy
  • Copper
  • Aluminum

14: Pressure vessels with an internal volume of 10 cubic feet or more

  • shall use rupture discs or duel pressure relief valves
  • shall use pressure relief devices or fusible plugs
  • shall use fusible plugs
  • shall use pressure relief devices

15: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.

  • of Group B2 refrigerant shall be prohibited
  • shall not be prohibited
  • shall be prohibited
  • containing R-11, R-123 & R-717 exclusively shall not be prohibited

16: All serviceable components of a refrigeration system shall be provided with

  • manufactures instructions on start-up procedures
  • service manuals
  • name plates with markings referring to pressure and temperature in accordance with ASME Boiler and Pressure Vessel Code
  • safe access

17: Large Mercantile occupancy is a premise or that portion of a premise where more than ____ persons congregate on levels above or below the street level to purchase personal merchandise.

  • 350
  • 250
  • 100
  • 400

18: R-123 belongs to Group

  • B-3
  • A-3
  • B-2
  • B-1

19: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested

  • regularly
  • quarterly
  • annually
  • bi-annually

20: _____ alloys shall not be used in contact with an halogenated refrigerants.

  • Nickel
  • Zinc
  • Copper
  • Magnesium

21: A class B2 refrigerant is considered

  • non-toxic and highly flammable
  • non-toxic and non-flammable
  • toxic and non-flammable
  • toxic and somewhat flammable

22: The color code of a tank of ammonia is

  • light green
  • silver
  • lavender
  • white

23: When is the only time you can leave a service container attached to a system?

  • Leaking system
  • Recovery
  • Charging
  • Both b and c

24: Pressure limiting devices are not required for systems containing less then ________ refrigerants.

  • 6.6 lbs
  • 13.9 lbs
  • 44 lbs
  • 22 lbs

25: The dial of a pressure gauge, when installed on the high side of a system be graduated 1.2 times the designed pressure.

  • True
  • False