ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: What pipe can not be used for refrigeration?

  • L
  • M
  • N
  • K

2: A premise where large numbers of people congregate and from which occupants can not quickly vacate the space is considered

  • public assembly occupancy
  • institutional occupancy
  • commercial occupancy
  • mixed occupancy

3: What was the main reason for enacting the no venting rule of July 1, 1992?

  • Ozone depletion
  • Green house effect
  • Global warming potential
  • All of the above

4: What must be done to refrigerant pipes before being buried?

  • Certified
  • Leaked checked
  • Coated
  • Encased

5: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.

  • 15
  • 75
  • 55
  • 50

6: Indirect systems using Group II refrigerants

  • shall be used in refrigeration system in excess of 1,000 lbs
  • shall be used for mechanical equipment only
  • shall be used in refrigeration system less than 1,000 lbs
  • shall have all refrigerant containing parts except piping, installed in a Class T machine room

7: Trichlorofluoromethane is the name of what refrigerant?

  • R-502
  • R-11
  • R-12
  • R-113

8: Can ammonia be used on domestic system?

  • yes, for systems under 10 tons
  • no
  • yes
  • no, unless there is proper ventilation system installed

9: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of

  • the high side
  • the aggregate of the high side and low side
  • 2.5 times the design pressure
  • the low side

10: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.

  • 24
  • 48
  • 36
  • 18

11: Low temperature systems should have what?

  • High pour point
  • Low pour point
  • High viscosity
  • None of the above

12: How far from the ground does a relief valve need to be?

  • At least 15' above grade
  • Not more than 3' above grade
  • At least 20' above grade
  • At least 25' above grade

13: Refrigeration devices shall be equipped with a ____ to protect against unexpected pressure due to a malfunction or fire?

  • T&P device
  • Temperature limiter device
  • Relief valve
  • Circuit Breaker

14: Halogenated refrigerants cannot be used with what material?

  • Stainless steel
  • Magnesium alloy
  • Aluminum
  • Copper

15: Relief valves are rated in

  • gallons of water per hour
  • gallons of water per minute
  • pounds of air per minute
  • pounds of air per hour

16: Liquid level gauges must be provided with what?

  • A relief valve
  • A low level mark
  • Automatic shut-offs
  • A red line

17: Where are the three places that the discharge from an ammonia relief valve be piped?

  • To chemical neutralizing tank only
  • Underground, into drain, into mechanical room
  • Atmosphere, Tank containing water, where the AHJ indicates.
  • None of the above.

18: Pressure vessels having an inside diameter of 6” or less shall be protected by

  • either a fusible plug or a pressure relief device
  • a fusible plug
  • a pressure relief device
  • Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified

19: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?

  • A group sensing
  • phosgene gas sening
  • refrigerant sensing
  • CO Sensing

20: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.

  • 80
  • 110
  • 90
  • 100

21: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.

  • 550
  • 100
  • 350
  • 50

22: When is the only time you can leave a service container attached to a system?

  • Leaking system
  • Recovery
  • Charging
  • Both b and c

23: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within

  • 2 months
  • 30 days
  • 1 week
  • 14 days

24: Fusible plugs shall not be used with pressure vessels of

  • 3 cubic feet or more
  • 15 square feet or less
  • 3 cubic feet or less
  • 15 cubic feet or more

25: Class T machine room

  • shall have refrigerant leak detecting systems installed inside and outside the room
  • shall have remote controls to stop the action of the refrigerant compressor
  • has no flame producing apparatus permanently installed
  • shall include closets used for setting equipment