ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.

  • 50
  • 550
  • 100
  • 350

2: Joints in refrigeration piping must be _____ before being covered?

  • Leak tested
  • Inspected
  • Pressurized
  • Insulated

3: Systems containing more than 110 pounds must have stop valves located at the

  • compressor suction inlet
  • compressor discharge outlet
  • receiver inlet and outlet
  • All of the above

4: A declaration test is needed when the system contains more than

  • 110 lbs
  • 120 lbs
  • 55 lbs
  • 65 lbs

5: Direct systems using Group II refrigerants

  • shall be allowed to be used for human comfort.
  • shall be installed per instruction of the AHJ
  • shall not be used for air condition for human comfort
  • shall be installed in Class T machinery rooms

6: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8

  • low side of the system
  • the vapor side of the system
  • high side of the system
  • the liquid side of the system

7: Pipe identification labels are required when the system contains more than

  • 65 lbs
  • 120 lbs
  • 110 lbs
  • 55 lbs

8: What type of material can't be used on the outlet of a relief valve?

  • Magnesium alloy
  • PVC
  • Copper
  • Stainless steel

9: Each machinery room shall contain

  • a refrigerant detector located in an area where the refrigerant from a leak will concentrate
  • smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
  • a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
  • high and low pressure controls

10: The gauge thickness required on a CO2 tank construction is

  • 5/16"
  • 1/8"
  • 1/16"
  • 3/32"

11: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?

  • 100,000
  • 100
  • 10,000
  • 1,000

12: What section governs pressure vessels?

  • OSHA
  • Section 1 ASHREA 15 ASME fired
  • Section ASHREA 34
  • Section 8 ASHREA 15 ASME unfired

13: An example of direct system is

  • rooftop unit
  • chiller
  • absorber
  • none of the above

14: Pressure vessels with an internal volume of 3 cubic feet or less

  • do not need pressure relief protection
  • shall use pressure relief devices or fusible plugs
  • shall use fusible plugs
  • shall use pressure relief devices

15: How many gallons of water per pound of ammonia do you need?

  • 20
  • 15
  • 1
  • 5

16: When an inspection is needed, how often must it be done?

  • every 18 months
  • annually
  • every 24 months
  • every 36 months

17: Which refrigerant class listed below is the most flammable?

  • A2
  • B2
  • A3
  • C3

18: What must be done to refrigerant pipes before being buried?

  • Coated
  • Encased
  • Certified
  • Leaked checked

19: R-11 belongs to Group

  • A-1
  • B-3
  • B-1
  • A-2

20: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the

  • evaporator
  • compressor
  • outside the machinery room
  • boiler

21: Who approves containers for refrigerants?

  • D.O.E
  • D.O.D
  • D.O.T
  • E.P.A

22: Name an HCFC refrigerant(s):

  • R-22
  • R-123
  • R-11
  • both a & b

23: Pressure relief valves shall be marked with the data from

  • Section XIII Division of the ASME Boiler & Pressure Code
  • Section VIII Division of the ASME Boiler & Pressure Code
  • Section I Division VIII of ASME Boiler & Pressure Code
  • Section IV Division of the ASME Boiler & Pressure Code

24: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by

  • District Engineering Inspectors
  • Commissioned Inspectors
  • Master licensed Technician
  • both a or b

25: Where must a refrigeration contractor's license number be displayed?

  • Trucks, license plates, and uniforms
  • Truck, office, every job, and on all equipment
  • Uniforms, checks, and invoices.
  • Trucks, invoices, and advertising