Topics: ASHRAE/CMR
1: Walls and doors of a machinery room shall be at least _____ hour(s) fire rated.
- 1
- 3
- 5
- 2
2: What pipe can not be used for refrigeration?
- L
- M
- K
- N
3: What is R-290’s ASHRAE safety code?
- A3
- B2
- B1
- A2
4: What is R-611’s ASHRAE Safety Code?
- B3
- C3
- A2
- B2
5: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.
- 15
- 50
- 55
- 75
6: Class A refrigerants are considered
- non-flammable
- toxic
- non-toxic
- flammable
7: Fusible plugs shall not be used with pressure vessels of
- 3 cubic feet or less
- 15 cubic feet or more
- 15 square feet or less
- 3 cubic feet or more
8: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 66
- 50
- 22
- 25
9: When an inspection is needed, how often must it be done?
- every 18 months
- annually
- every 24 months
- every 36 months
10: What refrigerant were phased out in 2004?
- R-22
- R-134a
- R-12
- R-11
11: How many refrigerant classifications are there for flammability?
- 7
- 1
- 3
- 2
12: A room having machinery but no flame producing apparatus permanently installed and operated is considered a
- Class B machinery room
- Class M machinery room
- Class A machinery room
- Class T machinery room
13: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.
- Machinery rooms need not be vented
- the return air ducted system
- the mechanical room housing the refrigeration system
- the outdoors
14: R-11 belongs to Group
- A-1
- B-3
- B-1
- A-2
15: What is the intention of the word “should” as used in the code?
- A mandatory requirement
- A recommendation or advisory guideline
- A technician’s choice of how it should be done
- None of the Above
16: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 550
- 100
- 350
17: What is Trichlorotrifluoromethane?
- R-12
- R-113
- R-11
- R-13
18: Stop valves shall not be permitted between the system and the
- service valve
- bleed valve
- relief valve
- condenser
19: What must be done to all doors and access points in duct work going through a mechanical room?
- Must be hindged
- Must be screwed shut
- Must be sealed and gasketed
- All of the above
20: When this is installed on the high side of a system, it must be capable of reading 1.2 times the design pressure (ASHRAE 15 9.11.3)
- Pressure gauge
- Temperature gauge
- Sight glass gauge
- All of the above
21: Liquid level gauges must be provided with what?
- A red line
- A relief valve
- Automatic shut-offs
- A low level mark
22: R-22 falls under which safety classification?
- B-1
- A-1
- A-2
- B-2
23: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- the vapor side of the system
- high side of the system
- the liquid side of the system
24: Which refrigerant replaced R-12?
- R-134A
- R-22
- R-410A
- R-407A
25: A relief valve shall be located at least ___ above grade.
- 15'
- 10'
- 36'
- 25'