Topics: ASHRAE/CMR
1: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
2: Pipe identification labels are required when the system contains more than
- 65 lbs
- 110 lbs
- 120 lbs
- 55 lbs
3: What is the intention of the word “should” as used in the code?
- A mandatory requirement
- A recommendation or advisory guideline
- A technician’s choice of how it should be done
- None of the Above
4: Refrigeration devices shall be equipped with a ____ to protect against unexpected pressure due to a malfunction or fire?
- T&P device
- Circuit Breaker
- Temperature limiter device
- Relief valve
5: All electrical work done on refrigeration systems must comply with
- OSHA
- Department of Energy
- ASHREA-15 Section 9.2.1
- NEC and Massachusetts Modifications
6: When an inspection is needed, how often must it be done?
- annually
- every 18 months
- every 24 months
- every 36 months
7: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with R-11
- Flush with RX-11
- Flush with R-718
- Flush with ammonia
8: When a pressure gauge is permanently installed on a system, it must be ___ times the design pressure of the system.
- 1.2
- 2.2
- 1.5
- 1
9: How are refrigerant blends classified?
- Based on worst case fractionation
- Based on best case Fractionation
- Based on the oil used
- Blends don't have to be classified
10: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- shall be inspected by the Boiler of Inspectors bi-annually
- shall have a pressure limiting device and a pressure relief valve installed
- shall have a pressure limiting device installed on the high side of the system
- does not require a pressure-limiting device
11: Group A2 refrigerants have a ______ toxicity rating than Group B1 refrigerants.
- the same
- higher
- lower
- there is no Group B1 refrigerants
12: What pipe can not be used for refrigeration?
- N
- L
- K
- M
13: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
14: What is the refrigerant chlorodifluoromethane?
- R-22
- R-12
- R-134a
- R-123
15: Who authorizes changes to the safety codes?
- Person who pulled the permit
- Board of Boilers
- Contractor who last serviced the system.
- Person in charge of the facility
16: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- low side of the system
- high side of the system
- the liquid side of the system
- the vapor side of the system
17: R-11 belongs to Group
- B-3
- A-2
- B-1
- A-1
18: What type of relief valve is used on low pressure centrifugal compressor systems?
- Spring-loaded relief valve
- Rupture disc
- Purge relief
- None of the above
19: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.
- 80%
- 100%
- 90%
- 75%
20: R-410A is classified as a ____ refrigerant on the safety matrix.
- B-2
- A-1
- B-1
- A-2
21: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of
- the aggregate of the high side and low side
- the low side
- the high side
- 2.5 times the design pressure
22: Evaporators located ____inches of a heating coil shall be equipped whit a pressure relief device.
- 18
- 10
- 15
- 24
23: A total of all group A-2,B-2, A-3, and B-3 refrigerants shall not exceed ____ lb in the occupied areas and machinery rooms of institutional occupancies.
- 50
- 100
- 350
- 550
24: When a receiver is greater than 3 cubic feet but less than 10 cubic feed, what is the minimum relief device required?
- fusible plug
- relief valve
- rupture disc
- all of the above
25: Evaporators within 18" of a heating coil must be equipped with a
- pressure relief device
- zone valve
- low limit control
- high limit control