Topics: ASHRAE/CMR
1: How many groups of refrigerants are there?
- 7
- 1
- 5
- 3
2: Institutional occupancy is
- a premise or that portion of a premise where large numbers of people congregate and from which occupants cannot quickly vacate the space.
- a premise or that portion of a premise from which, because they are disabled, debilitated, or confined, occupants cannot readily leave without the assistance of others.
- a premise or that portion of a premise where people transact business, receive personal service, or purchase food and other goods.
- None of the above
3: The main cause of enacting the "no vending rule" of July 1st 1992 was
- global warming potential
- ozone depletion
- both a & b
- None of the above
4: R-718 is rated unlimited for refrigeration quantity contained in a system. Why?
- R-718 is not rated unlimited because it's a dangerous refrigerant
- Because it's water
- Because it's a non-flammable refrigerant
- Because it's cheap
5: All welding done on any refrigeration system or piping covered by 522 CMR 9.00 shall be performed by a according to Section IX of the ASME code
- licensed technician
- licensed welder
- welder qualified
- competent welder
6: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by
- District Engineering Inspectors
- Commissioned Inspectors
- Master licensed Technician
- both a or b
7: A person holding a license as a refrigeration technician may connect or disconnect for the purpose of installation, repair, or replacement, any electrical device or control to be a part of a refrigeration or air conditioning system, from the
- first disconnect in
- breaker panel in
- load-side of the contactor in
- 24 volt secondary side of the Class 2 transformer to the thermostat
8: When should a relief valve start to function?
- Two times it's working pressure
- 10 psi before it's set pressure
- At it's set pressure
- Before the purge station discharges
9: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 100,000
- 1,000
- 100
- 10,000
10: How much refrigerant can be stored in a mechanical room outside of the system?
- 150
- 330
- 200
- 100
11: A plug containing an alloy that will melt at a specific temperature to relief pressure is a
- relief plug
- fusion plug
- rupture plug
- fusible plug
12: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
13: What refrigerant doesn't have to be classified?
- R-718
- R-134A
- R-717
- R-422A
14: Name a CFC refrigerant(s):
- R-11
- R-12
- R-123
- both a & b
15: What refrigerant were phased out in 2004?
- R-134a
- R-11
- R-12
- R-22
16: Evaporators within 18" of a heating coil must be equipped with a
- low limit control
- pressure relief device
- high limit control
- zone valve
17: How many different groups of refrigerants are there?
- 11
- 3
- 15
- 7
18: Which occupancy can ammonia be used in?
- industrial
- commercial
- depends on the quantity of freon
- redifential
19: Joints in piping for refrigeration containing parts must withstand temperatures of ___?
- 800F
- 700F
- 600F
- 1000F
20: Fusible plugs shall not be used with pressure vessels of
- 15 cubic feet or more
- 3 cubic feet or less
- 15 square feet or less
- 3 cubic feet or more
21: Where a refrigeration or air conditioning system is installed,
- A field inspection shall be made before it is put into service
- it shall not be operated below prescribed pressuers
- the form or certificate shall be authorized by the Department of Public Safety
- The company who installed the system must notify the fire department in the jurisdiction where installed
22: R-11 belongs to Group
- A-1
- B-1
- B-3
- A-2
23: Each machinery room shall contain
- a toxicity detector where the presence of ammonia or lithium bromide from a leak will concentrate
- smoke and fire alarms as well as three means of egress and that egress must meet 528 CMR ventilation requirements
- a refrigerant detector located in an area where the refrigerant from a leak will concentrate
- high and low pressure controls
24: Ashrae states that the equipment on a building needs to conform to adjacent buildings classifications when within ____ feet from opening and intakes.
- 20
- 75
- 50
- 15
25: Machinery rooms must be vented to ______?
- outdoors
- unoccupied spaces
- basement
- neutralizing tank