Topics: ASHRAE/CMR
1: Where are the three places that the discharge from an ammonia relief valve be piped?
- To chemical neutralizing tank only
- Underground, into drain, into mechanical room
- Atmosphere, Tank containing water, where the AHJ indicates.
- None of the above.
2: Refrigerant systems containing Group I refrigerants can be installed in or on public stairways.
- True
- False
3: Low temperature systems should have what?
- High pour point
- Low pour point
- High viscosity
- None of the above
4: The Department that certifies the transportation of refrigerant is the
- EPA
- DOT
- EPO
- RSES
5: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- does not require a pressure-limiting device
- shall have a pressure limiting device and a pressure relief valve installed
- shall have a pressure limiting device installed on the high side of the system
- shall be inspected by the Boiler of Inspectors bi-annually
6: All machine rooms must be outfitted with a detector that _______?
- activates an audible alarm
- activates a visual alarm
- starts the ventilation system
- All of the above
7: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
8: How many flammability classifications are refrigerants in?
- 2
- 7
- 5
- 3
9: It shall be the duty of the person in charge of the premises on which a refrigeration system containing more than ___ lbs of refrigerant is installed to provide a schematic drawing or panel giving directions for the operation of the system.
- 75
- 55
- 15
- 50
10: A pressure-limiting device isn't required on a factory-sealed system containing less than ____ lbs.
- 66
- 50
- 25
- 22
11: Field Inspections of refrigeration and A/C systems in Massachusetts shall be made by
- District Engineering Inspectors
- Commissioned Inspectors
- Master licensed Technician
- both a or b
12: System design pressures must take into consideration, not only, pressures found during normal operation but also what?
- When it's cold out
- When there is a malfunction on the high side
- When its warm out
- All of the above
13: Refrigerants shall be classified by
- maximum permissible quantities of each group
- color codes
- toxicity and flammability
- requirements for commercial, industrial, and residential occupancies
14: When systems are protected by a high pressure relief device, the compressor's pressure limiting device shall be set at or below ____ % of the operating pressure of the high side relief device.
- 80
- 110
- 100
- 90
15: Pipe identification labels are required when the system contains more than
- 120 lbs
- 55 lbs
- 65 lbs
- 110 lbs
16: When an inspection is needed, how often must it be done?
- every 24 months
- annually
- every 36 months
- every 18 months
17: A High-Probablity system
- is such that a leak of refrigerant from failed connections will enter the unoccupied space
- is such that any leak will cause injury or death to anyone within a 100 square foot area
- is such that a leak of refrigerant from failed connections will enter the occupied space
- is a system highly likely to leak from a failed connection or component of such system
18: Pressure vessels with an internal volume of 3 cubic feet or less
- do not need pressure relief protection
- shall use fusible plugs
- shall use pressure relief devices or fusible plugs
- shall use pressure relief devices
19: What is R-22?
- CCFCM
- HFC
- Chlorofluoromethane
- Chlorodifluoromethane
20: Insurance companies shall forward each inspection report of all refrigeration or A/C systems to the Chief of Inspections within
- 1 week
- 2 months
- 30 days
- 14 days
21: According to ASHRAE Standard-15 9.8 Positive Displacement Compressor Protection, the pressure-relief device discharge into
- the low-pressure side of the system
- the high side of the system
- the liquid receiver
- both a and c are correct
22: A declaration test is needed when the system contains more than
- 65 lbs
- 55 lbs
- 120 lbs
- 110 lbs
23: What do you need to do when you install a new system?
- Have it inspected
- Add refrigerant
- Insulate the suction line before you take a superheat reading
- Document the superheat and subcooling reading
24: All electrical work done on refrigeration systems must comply with
- Department of Energy
- ASHREA-15 Section 9.2.1
- NEC and Massachusetts Modifications
- OSHA
25: The color code of a tank of ammonia is
- silver
- white
- lavender
- light green