ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: What refrigerant doesn't have to be classifted?

  • R-711
  • R-134a
  • R-717
  • R-718

2: How many refrigerant classifications are there for toxicity?

  • 1
  • 5
  • 2
  • 3

3: R-410A is classified as a ____ refrigerant on the safety matrix.

  • A-1
  • A-2
  • B-1
  • B-2

4: Pressure limiting devices are not required for systems containing less then ________ refrigerants.

  • 22 lbs
  • 6.6 lbs
  • 13.9 lbs
  • 44 lbs

5: High pressure controls should be set no higher than

  • 80% of set point
  • 90% of set point
  • 10% of set point
  • 25% of set point

6: A pressure relief should be located at least _______ from windows and doors.

  • 30'
  • 25'
  • 20'
  • 15'

7: System design pressures must take into consideration, not only, pressures found during normal operation but also what?

  • When it's cold out
  • When there is a malfunction on the high side
  • When its warm out
  • All of the above

8: A class A3 refrigerant is considered

  • non-toxic but highly flammable
  • toxic and non-flammable
  • toxic and somewhat flammable
  • non-toxic and non-flammable

9: What do you need to do when you install a new system?

  • Add refrigerant
  • Insulate the suction line before you take a superheat reading
  • Document the superheat and subcooling reading
  • Have it inspected

10: How many gallons of water per pound of ammonia do you need?

  • 5
  • 20
  • 15
  • 1

11: When must refrigeration system covered by the code be inspected?

  • Annually
  • Annually and when installed
  • Not required
  • Upon installation

12: A “U” or “UM” marking a on a nameplate of a pressure vessels signifies compliance with Section VIII of

  • the ASME Boiler and Pressure Vessel Code
  • Section 11.3.1.5 ASHRAE 15 Standard
  • the ANSI Standard 10.7.2
  • both the ANSI Standard 10.7.2 and ASHRAE 15 Standard 11.3.1.5

13: Pressure vessels with an internal volume of 3 cubic feet or more

  • shall use pressure relief devices
  • do not need pressure relief protection
  • shall use pressure relief devices or fusible plugs
  • shall use fusible plugs

14: R-22 is considered a(n)

  • HFC
  • HCFC
  • HCFCH
  • CFC

15: Methyl Chloride is a halogenated refrigerant and should not come in contact with

  • aluminum
  • zinc
  • magnesium
  • all of the above

16: What is R-22?

  • Chlorodifluoromethane
  • Chlorofluoromethane
  • CCFCM
  • HFC

17: What should not (and can not) be located between a pressure imposing device and a pressure-limiting device?

  • Foot valve
  • Muffler
  • Stop valve
  • Moisture indicator

18: The 522 CMR 9.00 has adopted for reference ASHRAE ____

  • 10
  • 15
  • III
  • 25

19: How many groups of refrigerants are there?

  • 7
  • 5
  • 1
  • 3

20: Pressure vessels having an inside diameter of 6” or less shall be protected by

  • a pressure relief device
  • a fusible plug
  • Pressure vessels having an inside diameter of 6” or less need no such protection unless otherwise specified
  • either a fusible plug or a pressure relief device

21: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere

  • 1,000
  • 6.6
  • 110
  • 330

22: Halogenated refrigerants cannot be used with what material?

  • Aluminum
  • Copper
  • Stainless steel
  • Magnesium alloy

23: When is the space above a drop ceiling calculated as space for refrigerant limit quantities?

  • When it's used as part of a supply or return air system
  • When its white
  • When there is a space 6' or more above it
  • When there are sprinklers above

24: What refrigerant doesn't have to be classified?

  • R-718
  • R-422A
  • R-717
  • R-134A

25: According to the 522 CMR Board of Boilers, refrigerant detectors, alarms, and the refrigeration mechanical room ventilating systems shall be tested

  • annually
  • regularly
  • quarterly
  • bi-annually