ASHRAE/CMR code Prep Quiz

Topics: ASHRAE/CMR

Quiz Result Settings

1: Pressure vessels with an internal volume of 10 cubic feet or more

  • shall use fusible plugs
  • shall use pressure relief devices
  • shall use rupture discs or duel pressure relief valves
  • shall use pressure relief devices or fusible plugs

2: How many gallons of water do you need per pound of ammonia?

  • 10
  • 100
  • 50
  • 1

3: Name three things that must be done when changing refrigeration lubricant?

  • Nothing must be done
  • Make sure it's compatible, notify owner, notify AHJ
  • You can't change lubricants.
  • Place sign, check for leaks, insulate

4: Can you use Ammonia in industrial applications?

  • No, never
  • Yes, Under certain condidtions
  • Yes, always
  • When mixed with R-718

5: Machinery rooms shall be vented to _____________ and utilizing mechanical ventilation.

  • the outdoors
  • Machinery rooms need not be vented
  • the return air ducted system
  • the mechanical room housing the refrigeration system

6: Joints in piping for refrigeration containing parts must withstand temperatures of ___?

  • 700F
  • 800F
  • 600F
  • 1000F

7: Pressure vessels nameplate markings must be compliant with the

  • ASHRAE 34 Standards
  • CMR-588 & CMR-528
  • ASME Boiler and Pressure Vessel Code
  • All of the Above

8: A class B2 refrigerant is considered

  • toxic and non-flammable
  • toxic and somewhat flammable
  • non-toxic and non-flammable
  • non-toxic and highly flammable

9: R-717 is

  • water
  • trichloromethane
  • carbon dioxide
  • ammonia

10: All machine rooms must be outfitted with a detector that _______?

  • activates an audible alarm
  • activates a visual alarm
  • starts the ventilation system
  • All of the above

11: When a refrigeration or air conditioning system is installed

  • it shall not be operated below prescribed pressures
  • a field inspection shall be made before it is put into service
  • it shall be approved by the owner for proper operation.
  • the form of certificate shall be authorized by the Department of Pubic safety

12: Pipe identification labels are required when the system contains more than

  • 110 lbs
  • 120 lbs
  • 55 lbs
  • 65 lbs

13: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?

  • 10,000
  • 1,000
  • 100,000
  • 100

14: What pipe can not be used for refrigeration?

  • L
  • N
  • K
  • M

15: An evaporator coil located near heating coil shall have a pressure-relief device installed within ______ inches of the evaporator.

  • 18
  • 36
  • 24
  • 48

16: What must be done to refrigerant pipes before being buried?

  • Coated
  • Leaked checked
  • Encased
  • Certified

17: Where a refrigeration or air conditioning system is installed,

  • the form or certificate shall be authorized by the Department of Public Safety
  • it shall not be operated below prescribed pressuers
  • The company who installed the system must notify the fire department in the jurisdiction where installed
  • A field inspection shall be made before it is put into service

18: All serviceable components of a refrigeration system shall be provided with

  • service manuals
  • safe access
  • name plates with markings referring to pressure and temperature in accordance with ASME Boiler and Pressure Vessel Code
  • manufactures instructions on start-up procedures

19: pressure relief valves must discharge to the atmosphere at a location not less than 15 feet from ground level and ____ feet from any window, ventilation opening, or exits of buildings.

  • 10
  • 25
  • 15
  • 20

20: When must refrigeration system covered by the code be inspected?

  • Annually
  • Annually and when installed
  • Not required
  • Upon installation

21: Pressure relief valves shall be marked with the data from

  • Section XIII Division of the ASME Boiler & Pressure Code
  • Section I Division VIII of ASME Boiler & Pressure Code
  • Section VIII Division of the ASME Boiler & Pressure Code
  • Section IV Division of the ASME Boiler & Pressure Code

22: Liquid shall not occupy more than ____ of the volume when the temperature of the refrigerant is 90F.

  • 75%
  • 80%
  • 90%
  • 100%

23: The ____ design is the maximum pressure for which a specific part of a refrigeration system is designed.

  • design pressure
  • low pressure
  • critical pressure
  • high pressure

24: R-410A is classified as a ____ refrigerant on the safety matrix.

  • B-1
  • A-2
  • A-1
  • B-2

25: What is the refrigerant dichlorodifluoromethane?

  • R-12
  • R-123
  • R-22
  • R-134A