Topics: ASHRAE/CMR
1: When a receiver is greater than 3 cubic feet but less than 10 cubic feed, what is the minimum relief device required?
- fusible plug
- relief valve
- rupture disc
- all of the above
2: A class A3 refrigerant is considered
- toxic and somewhat flammable
- non-toxic but highly flammable
- non-toxic and non-flammable
- toxic and non-flammable
3: What does safe access mean?
- A clear unobstructed path to the equipment and controls
- OSHA approved
- Well-lit exit signs
- Locked doors
4: No open flames are allowed in the machinery room unless?
- Only when combustion air is provided from outside of the machinery room
- Approved by the installing contractor
- Never can be allowed
- Approved by the authorized person
5: Ammonia can come in contact with _______ ?
- Copper
- Copper tubing
- Aluminum
- Brass
6: A Category D fluid
- is when the fluid handled is non flammable, nontoxic, and not damaging to human as defined in ANSI/ASME Process Piping.
- is when the design pressure does not exceed 150 psi
- a fluid for service piping in which the potential for personnel exposure is judged to cause harm and irreversible damage to those persons exposed to it
- Both a and b are correct
7: Whoever owns/uses a refrigeration or air conditioning system covered by this code
- must notify the Department of Public Safety prior to starting the system
- shall be licensed by the Commonwealth of Massachusetts according to CMR 522
- shall make application for inspections to the Chief of Inspectors
- None of the above
8: What is the minimum size of the discharge pipe?
- Same size as the outlet of the relief valve
- One pipe size larger that the inlet of the relief valve
- Depends on size of manifold
- All of the above
9: When can recovered refrigerants be reused?
- They can't
- Only when used in original owner's equipment
- Only if used in 30 days of recovery
- None of the above
10: What is not a requirement of a class T machine room?
- automatic ventilation
- self-closing doors
- fire hose connection to the building fire protection system
- tight fitting doors
11: Before you change the type of refrigerant in a refrigeration system, what three things must be done?
- Place sign, check for leaks, and insulate suction line
- Make sure its compatible, notify owner, and notify AHJ.
- you can never change refrigerants
- Nothing must be done
12: Direct systems using Group II refrigerants
- shall not be used for air condition for human comfort
- shall be installed in Class T machinery rooms
- shall be allowed to be used for human comfort.
- shall be installed per instruction of the AHJ
13: When this is installed on the high side of a system, it must be capable of reading 1.2 times the design pressure (ASHRAE 15 9.11.3)
- Pressure gauge
- Temperature gauge
- Sight glass gauge
- All of the above
14: R-22 is considered a(n)
- HFC
- HCFCH
- CFC
- HCFC
15: What would be the classification for Stop & Shop grocery store?
- Industrial
- Large mercantile
- Instituional
- Place of assembly
16: Can a R22 line set be reused for a 410A system and if it can be reused, what must be done to it?
- Flush with R-11
- Flush with RX-11
- Flush with ammonia
- Flush with R-718
17: Which refrigerant(s) is an HFC?
- R-22
- R-410A
- R-502
- All of the above
18: Name an HCFC refrigerant(s):
- R-22
- R-123
- R-11
- both a & b
19: A pressure relief should be located at least _______ from windows and doors.
- 15'
- 20'
- 30'
- 25'
20: A 3-cubic foot receiver must have what type of relief valve?
- fusible plug
- relief valve
- rupture device
- none of the above
21: When should a relief valve start to function?
- 10 psi before it's set pressure
- Two times it's working pressure
- Before the purge station discharges
- At it's set pressure
22: The ASHRAE Standard 34 requires what type of alarm for equipment rooms using HCFC-123?
- CO Sensing
- A group sensing
- phosgene gas sening
- refrigerant sensing
23: What is the refrigerant chlorodifluoromethane?
- R-123
- R-134a
- R-22
- R-12
24: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 6.6
- 330
- 110
- 1,000
25: How many flammability classifications are refrigerants in?
- 5
- 2
- 7
- 3