Topics: ASHRAE/CMR
1: A machine room with a refrigerant system using ammonia shall
- be provided with a continuously operated ventilation system
- be considered a non-hazardous location in accordance with National Electrical code
- have no flame producing apparatus permanently installed and operated
- All of the above
2: Before determining if a machinery room equipment is excluded from following Ashrae 15, you must determine how many pounds of refrigerant per _____ cubic feet?
- 100
- 10,000
- 100,000
- 1,000
3: A factory-sealed system containing less than 22lbs. of Group A1 refrigerant
- does not require a pressure-limiting device
- shall have a pressure limiting device and a pressure relief valve installed
- shall have a pressure limiting device installed on the high side of the system
- shall be inspected by the Boiler of Inspectors bi-annually
4: Setting a pressure relief device shall not exceed ___ of the design pressure
- 100%
- 75%
- 90%
- 80%
5: The certificate of inspection
- shall be $20 and an additional fee of $1 for each tone above 20 tons
- shall be authorized by a notarized insurance company
- shall be posted and protected from dirt, water, and other elements
- shall be posted on the compressor shell or electrical panel at the unit
6: The pressure relief device of a positive displacement compressor shall discharge in the ______________or in accordance with 9.7.8
- the liquid side of the system
- low side of the system
- the vapor side of the system
- high side of the system
7: What is a Category "M" fluid?
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily content
- A typical refrigerant used on newer air conditioning and heat pump systems
- Any fluid that exceeds 150 psig and has design temperatures over 366F
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and the designed temperature is between -20F to 366F
8: Large vessels containing refrigerant ______________________ from using two or more pressure-relief devices in parallel to obtain the required capacity.
- containing R-11, R-123 & R-717 exclusively shall not be prohibited
- of Group B2 refrigerant shall be prohibited
- shall not be prohibited
- shall be prohibited
9: Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak over 55 lbs of refrigerant charge, shall be displayed on a conspicuous card located as near as possible to the
- outside the machinery room
- compressor
- boiler
- evaporator
10: What type of pressure relief device is used on a CO2 system?
- Fusible plug
- Rupture disk
- Gate valve
- Glove valve
11: Dual-pressure relief devices should be installed on
- vessels of 3 cubic feet or more
- vessels of 10 cubic feet or less
- vessels of 3 cubic feet or less
- vessels of 10 cubic feet or more
12: Group A1 refrigerants over ____ pounds in a system must discharge to the atmosphere
- 330
- 110
- 6.6
- 1,000
13: The color code of a tank of ammonia is
- lavender
- white
- light green
- silver
14: Can you use Ammonia in industrial applications?
- When mixed with R-718
- Yes, always
- No, never
- Yes, Under certain condidtions
15: A plug containing an alloy that will melt at a specific temperature to relief pressure is a
- relief plug
- fusion plug
- fusible plug
- rupture plug
16: What is a Category "D" fluid?
- Any fluid that exceeds 150 psig and has design temperature of over 366F
- A fluid which is nonflammable, nontoxic, not damaging to human tissues, does not exceed 150 psig, and design temperature is between -20F to 366F
- A typical refrigerant used on newer air conditioning and heat pump ssytems
- A toxic fluid, which can produce serious irreversible harm to persons on breathing or bodily contact
17: The main purpose of a refrigerant detector in a machinery room is to
- inform there is a refrigerant leak int he system
- detect toxins in the air caused by a refrigerant leak
- to set off an alarm when there is refrigerant present inside the room
- all of the above
18: When a refrigeration or air conditioning system is installed
- a field inspection shall be made before it is put into service
- the form of certificate shall be authorized by the Department of Pubic safety
- it shall not be operated below prescribed pressures
- it shall be approved by the owner for proper operation.
19: R-123 belongs to Group
- B-2
- A-3
- B-3
- B-1
20: Liquid level gauge glasses shall have automatic closing shut off valves, except Bull's eye or reflex type.
- True
- False
21: A premise or that portion of a premise where large numbers of people congregate and from which occupants cannot quickly vacate the space such as auditoriums, ballrooms, classrooms, passenger depots, restaurants, and theaters is considered a(n)
- illegal occupancy
- commercial occupancy
- institutional occupancy
- public assembly occupancy
22: Ammonia belongs to Group
- B-2
- B-1
- A-1
- A-2
23: A pressure relief should be located at least _______ from windows and doors.
- 20'
- 25'
- 15'
- 30'
24: Where a refrigeration or air conditioning system is installed,
- it shall not be operated below prescribed pressuers
- The company who installed the system must notify the fire department in the jurisdiction where installed
- A field inspection shall be made before it is put into service
- the form or certificate shall be authorized by the Department of Public Safety
25: What type of copper is not permitted on refrigeration systems?
- Type K
- Type N
- Type L
- Type M