Refrigeration RT/RC Prep Quiz

Topics: All categories in the pool

Quiz Result Settings

1: A chilled water pump's suction gauge reads 10 psig. The discharge gauge reads 48 psig. What is the head in feet the pump is working against?

  • 96
  • 88
  • 38
  • 58

2: If a low-pressure chiller has a low-side leak, which of the following will most likely result?

  • High head pressure and low suction pressure
  • Low suction pressure and low discharge pressure
  • Low head pressure and high suction pressure
  • High suction pressure and high discharge pressure.

3: The density of a gas refers to

  • pounds per cubic foot
  • cubic feet per pound
  • pounds per absolute pressure
  • pounds per square foot

4: Class A refrigerants are considered

  • non-flammable
  • non-toxic
  • toxic
  • flammable

5: R22 and 410A operate at the same range of condensing and evaporating temperatures

  • true
  • false

6: Pressure vessels with an internal volume of 3 cubic feet or less

  • do not need pressure relief protection
  • shall use fusible plugs
  • shall use pressure relief devices or fusible plugs
  • shall use pressure relief devices

7: The rupture disc on a low-pressure chiller typically releases pressure at

  • 0 psig
  • 15 psig
  • 10 psig
  • 5 psig

8: The 522 CMR 9.00 has adopted for reference ASHRAE ____

  • III
  • 25
  • 10
  • 15

9: The test pressure applied to the high side of each factory-assembled refrigerating system shall be at least equal to the design pressure of

  • the aggregate of the high side and low side
  • the high side
  • 2.5 times the design pressure
  • the low side

10: Lithium-bromide, Li-Br, is best characterized as a

  • sugar
  • salt
  • sand
  • soil

11: A room having machinery but no flame producing apparatus permanently installed and operated is considered a

  • Class T machinery room
  • Class B machinery room
  • Class M machinery room
  • Class A machinery room

12: Most CFC's are

  • toxic
  • inert
  • inert but toxic
  • flammable

13: In a horizontal shell & tube condenser, the ammonia is liquefied by

  • water sprayed over condenser
  • removing the latent heat of vaporization
  • passing thru the tubes from top to bottom
  • removing the latent heat of fusion

14: What are the three components of a transformer?

  • Contacts, secondary coil, and core
  • Primary coil, secondary coil, and copper contacts
  • Primary coil, secondary coil, and core
  • Primary core, secondary coil, and high and low voltage connectors.

15: Two capacitors are wired in parallel. One capacitor has a value of 15uf. The other has a value of 25uf. What is the total value supplied?

  • 40 uf
  • 25 uf
  • 20 uf
  • 15 uf

16: A machine room with a refrigerant system using ammonia shall

  • be provided with a continuously operated ventilation system
  • be considered a non-hazardous location in accordance with National Electrical code
  • have no flame producing apparatus permanently installed and operated
  • All of the above

17: R-12. R-22, and R-40 are considered Group I refrigerants.

  • True
  • False

18: How far from the ground does a relief valve need to be?

  • Not more than 3' above grade
  • At least 20' above grade
  • At least 15' above grade
  • At least 25' above grade

19: Which has more turns in the windings: Start windings or Run windings?

  • Start windings
  • Run windings
  • They both have the exact same turns
  • Depends on the system and capacitor used

20: How are a compressor and condenser fan wired?

  • parallel
  • series-parallel
  • series
  • parallel-series

21: Megaohm meters can detect a ground in the

  • 10,000,000 ohms or higher
  • up to 1,000,000 ohms
  • up to 1,000 ohms
  • up to 10,000 ohms

22: How many groups of refrigerants are there?

  • 5
  • 7
  • 3
  • 1

23: What is not a requirement of a Class T machine room?

  • Self-closing doors
  • Automatic ventilation
  • Fire hose connected to the building fire protection system.
  • Tight fitting doors

24: If a purge unit fails on a low pressure chiller, what are the symptoms?

  • low pressure chillers do not have purge units
  • increased capacity
  • low suction pressure
  • high head pressure

25: A declaration test is needed when the system contains more than

  • 120 lbs
  • 65 lbs
  • 55 lbs
  • 110 lbs